IM 01C22T01-01E

2-9

2. HART COMMUNICATOR OPERATION

(5) Damping Time Constants

The damping constant is set to 2.0 seconds at the
factory. When changing the damping constant, proceed
as follows:

1

F0215.EPS

Call up the

Damp

display.

EJA:
Damping
2.00 s
2.00

HELP

DEL

ESC

ENTER

Enter 0.2 and press ENTER (F4).

(ENTER)

‘0 . 2’

2

EJA:
Basic Setup
1 Unit kPa
2 Re-range
3 Device information
4 Xfer fncfn Linear
5 Damp 0.20s

HELP

SEND

HOME

ENTER

Press SEND (F2) to send the data
to the transmitter.

3

EJA:
Set to nearest
possible value
occurred writing Pres
damping
Press OK...

DEL

SET

ESC

OK

A confirmation display appears.
Press OK (F4), then check to
confirm that disappears.

(OK)

1. Device setup

3. Basic setup

6. Damp

SEND

Example: To change from 2.0 seconds to 0.2 seconds

NOTE

1. Only the damping constants listed in Table 2

are available. When a value not listed in
Table 2 is entered, the value in Table 2
nearest the entered value is set.

2. The damping constant set with the procedure

here is of the damping constant in the trans-
mission part (electric circuit). The damping
constant of the capsule assembly shall be
added to obtain the overall damping constant
of the transmitter.

Table 2

0.2 Sec
0.5 Sec
1.0 Sec
2.0 Sec
4.0 Sec
8.0 Sec

16.0 Sec
32.0 Sec
64.0 Sec

T0203.EPS

(6) Output Signal Low Cut Mode Setup

Low cut can be used on the output signal to stabilize
the output near the zero point.

The low cut point can be set in a range from 0 to 20%
of output. (Hysteresis of cut point: ±1%)

Either

LINEAR

or

ZERO

can be selected as the low

cut mode.

Unless otherwise specified, the cut mode is set to
LINEAR at the factory.

(%)

50

(%)

50

0

50

(%)

50

(%)

Output

Output

For low cut in linear mode

Input

20

20

0

For low cut in zero mode

Input

F0216.EPS

Example: To set the low cut range to 20% and the cut mode

to ZERO, proceed as follows:

Figure 2.2.2 Low Cut Mode

F0217.EPS

EJA:
Low cut
10.00%
10.00

HELP

DEL

ESC

ENTER

Call up the Low cut, and set to
20%.

(ENTER)

(ENTER)

‘2 0’

EJA:
Cut mode
Linear
Linear
Zero

HELP

SEND

ESC

ENTER

Select the Cut mode, and set to
Zero.

EJA:
Basic Setup
4 Device information
5 Xfer fnctn Linear
6 Damp 0.50s
7 Low cut 20.00 %
8 Cut mode Zero

DEL

SEND

HOME

OK

Press SEND (F2) to send the date,
then check to confirm that
disappears.

(SEND)

1. Device setup

3. Basic setup

7. Low Cut, 8. Cut mode

SEND