2. HART COMMUNICATOR OPERATION

(7) Bi-directional Flow Measurement

(a)

Bi-dir mode

enables selection of 50% output at an

input of 0 mmH

2

O.

F0218.EPS

(ENTER)

EJA:
Bi-dir mode
OFF
off
on

HELP

SEND

ESC

ENTER

Call up the Bi-dir mode Display
Select on, and press ENTER (F4).
Press SEND (F2) to send the data
to the transmitter, then check to
confirm that disappears.

(SEND)

1. Device setup

4. Detailed setup

2. Signal condition

8. Bi-dir mode

SEND

Note: The measurement range changes to –3000 to 0 to

3000mmH

2

O (output 0% to 50% to 100%).

Note that LRV and URV are not changed.

Example: If measurement range is 0 to 3000mmH

2

O

(LRV = 0 mmH

2

O, URV = 3000 mmH

2

O)

(b) Combining

Bi-dir mode

with

Xfer fnctn

provides

a square root output computed independently for
0% to 50% output and for 50% to 100% output.

20 mA (100% display)

4 mA (–100% display)

Output mode “LINEAR”

LRV

HRV

F0219.EPS

20 mA (100% display)

Low Cut

4 mA (–100% display)

Output mode “SQUARE ROOT”

LRV

HRV

(8) Change Output Limits

The range of normal ouput is preset at factory from
Ϫ5.0 to 110.0% unless otherwise specified or condi-
tioned, and the output is limited with these upper and
lower values. This output range can be changed, for
example, to meet the requirements of NAMUR, within
the settable range. Set the lower limit with

AO lower

limit %

and upper limit with

AO Upper Limit %

.

Settable range :

Ϫ5.0 to 110.0 (%),

Upper limit > Lower limit

(9) Integral Indicator Display Mode

F0220.EPS

(ENTER)

EJA:
Display fnctn
Linear
Linear
Square Root

HELP

SEND

ESC

ENTER

Select Square Root and press
ENTER (F4).
Press SEND (F2) to send data.

(SEND)

1. Device setup

4. Detailed setup

4. Display condition

2. Display fnctn

Example: Change from Linear to Sq root