2. HART COMMUNICATOR OPERATION

F02282.EPS

EJA:
Press OK when
pressure is stable

HELP

DEL

ABORT

OK

3

Press OK (F4).

EJA:
Enter applied
pressure value
0.00 mmH2O
0.00

HELP

ABORT

4

Enter 1000, and press ENTER (F4).
Remove pressure appears for a
while.
Fine input adjustment (0%) is
complete.

DEL

ENTER

(ENTER)

(OK)

‘1 0 0 0’

SPAN adjustment shall be carried out with

Upper

Sensor trim

. After selecting

Upper Sensor trim

,

apply a pressure of 3000 mmH

2

O (corresponding to

100% of the measurement range). Then, proceed the
same as for the operations for

Lower Sensor trim

.

1

F0229.EPS

Select the Upper Sensor trim item.

EJA:
Sensor trim
1 Zero Trim
2 Pres
3 Lower sensor trim
4 Upper sensor trim
5 Sensor trim points

HELP

SET

HOME

OK

EJA:
Apply hi pressure

DEL

SET

ABORT

OK

2

Apply a standard pressure of 300
mmH

2

O to the transmitter. After

obtaining a stable pressure, press
OK (F4).

EJA:
Press OK when
pressure is stable

HELP

DEL

ABORT

OK

3

Press OK (F4).

EJA:
Enter applied
Pressure value
0.00 mmH2O
0.00

HELP

ABORT

4

Enter 3000, and press ENTER (F4).
Remove pressure appears for a
while.
Fine input adjustment (100%) is
complete.

DEL

ENTER

(OK)

(OK)

(OK)

‘3 0 0 0’

(15) Trim Analog Output

Fine output adjustment is carried out with

D/A trim

or

Scaled D/A trim

.

• D/A Trim

D/A trim

is to be carried out if the calibration

digital ammeter does not read 4.000 mA and 20.000
mA exactly with the output signal of 0% and 100%.

• Scaled D/A Trim

Scaled D/A trim

is to be carried out if the output

is adjusted using a voltmeter or other types of
meters or using a meter whose the scale unit is 0 to
100%.

1

F0230.EPS

Select the D/A trim item.

EJA:
Trim analog output
1 D/A trim
2 Scaled D/A trim

HELP

SET

HOME

OK

EJA:
WARN-LOOP should be
removed from
automatic control

DEL

SET

ABORT

OK

2

Press OK (F4).

EJA:
Connect reference
meter

HELP

DEL

ABORT

OK

3

Connect the ammeter (

±

1

µ

A is

measurable), and press OK (F4).

EJA:
Setting fld dev
output to 4mA

HELP

ABORT

4

Press OK (F4), and the transmitter
outputs the output signal of 0%.

DEL

OK

(OK)

(OK)

(OK)

EJA:
Enter meter value

4.000

HELP

ESC

5

Enter the read value 4.115 of the
ammeter, and press ENTER (F4).
(The output of the transmitter
changes.)

DEL

ENTER

(ENTER)

‘4 . 1 1 5’

Example 1: For the adjustment using an ammeter (

±

1

µ

A is

measurable)

1. Device setup

2 Diag/Service

3. Calibration

2. Trim analog output

Ammeter reading: 4.115