15) burst mode, 16) multidrop mode, 16) burst mode -16 – Yokogawa EJA115 User Manual

Page 23

Advertising
background image

IM 01C22T01-01E

2-16

2. HART COMMUNICATOR OPERATION

F0233.EPS

EJA:
Enter meter value

1.000

HELP

ABORT

9

9

8

Enter the reading of the voltmeter
(1.010), and press ENTER (F4).
(The output of the transmitter
changes.)

DEL

ENTER

(ENTER)

(ENTER)

‘1 . 0 1’

EJA:
Scaled output: 1.000
equal readout
device?
1 Yes
2 No

HELP

ABORT

10

DEL

ENTER

Voltmeter reading: 1.010

Because the reading on the
voltmeter is 1.000, select Yes and
press ENTER (F4).
If the reading is not 1.000, select
No. Repeat steps and until
the voltmeter reads 1.000 V.

Voltmeter reading: 1.000

11

Press OK (F4). The output signal of
100% is output.

EJA:
Setting fld dev
output to 20mA

HELP

SET

ABORT

OK

EJA:
Enter meter value

5.000

HELP

DEL

ABORT

ENTER

12

EJA:
Scaled output: 5.000
equal readout
device?
1 Yes
2 No

HELP

DEL

ABORT

ENTER

13

EJA:
NOTE-Loop may be
returned to automatic
control

HELP

ABORT

14

Enter the reading of the voltmeter
(5.210), and press ENTER (F4).

DEL

OK

(ENTER)

“Returning fid dev to
original output”

(OK)

(ENTER)

‘5 . 2 1’

(OK)

Voltmeter reading: 5.210

Select Yes and press ENTER (F4).

Press OK (F4).

Voltmeter reading: 5.000

(16) Burst Mode

The transmitter continuously sends the data stored in it
when the burst mode is set on. Either one of measured
pressure variable, % output value, or 4 to 20 mA
output value can be selected and sent. The data is sent
intermittently as a digital signal at 75 ms intervals
when the transmitter is set in the burst mode. There-
fore, communication by the HART simultaneous
communicator is also possible.

Setting of Burst Mode

F0234.EPS

Call up the Burst option, and set
the data to be sent.
• Pressure variable (PV)
• % output value (% range/current)
• 4 to 20 mA output value (Process

vars/crnt)

EJA:
Burst option
********
PV
% range/current
Process vars/crnt

HELP

DEL

ESC

ENTER

EJA:
Burst mode
Off
On
Off

DEL

DEL

ESC

ENTER

Call up the Burst mode and set to
On.
Then, Press SEND (F2).

HELP

(ENTER)

(ENTER)

(SEND)

1. Device setup

4. Detailed setup

3. Output condition

4. HART output

3. Burst mode, 4. Burst option

To Release from the Burst Mode:

Call up the

Burst mode

display, and set to

OFF

.