2-17

2. HART COMMUNICATOR OPERATION

(17) Multidrop Mode

“Multidropping”

transmitters refers to the connection

of several transmitters to a single communications
transmission line. Up to 15 transmitters can be con-
nected when set in the multidrop mode. To activate
multidrop communication, the transmitter address must
be changed to a number from 1 to 15. This change
deactivates the 4 to 20 mA analog output, sending it to
4 mA. The alarm current also is disabled.

Setting of Multidrop Mode

F0235.EPS

Call up the Poll addr and set the
polling address. (a number from 1 to
15)
And press SEND (F2) to send the
data.

EJA:
Poll addr
O
0

HELP

DEL

ESC

ENTER

HART Communicator
Auto Poll
No
No
Yes

DEL

DEL

ESC

ENTER

Call up the Auto Poll and set to
Yes.

HELP

(ENTER)

1. Device setup

4. Detailed Setup

3. Output condition

4. HART Output

1. Poll addr

Online

Utility

Auto Poll

NOTE

1. When the address is set and the multi-drop

mode is set to “No” at the same time, Online
menus cannot be called up and displayed. Be
sure to turn the multidrop mode to “Yes” after
setting the address with “Poll addr.”

2. When the same polling address is set for two

or more transmitters in multidrop mode,
communication with these transmitters is
disabled.

1

1

1

F0236.EPS

(1) The HART communicator

searches for the transmitter that
is set in the multi-drop mode
when the HART communicator
is turned on.
When the HART communicator
is connected to the transmitter,
the manufacturer’s x’ter type
code and the tag will be
displayed (display ).

(2) Select the desired transmitter.

After that, normal
communication to the selected
transmitter is possible. However,
the communication speed is
slow in this case (display ).

(3) To communicate with another

transmitter, turn off the power
once and then turn on it again,
or call up display , and select
Online.

(4) Display will appear. Select

the desired transmitter.

HART Communicator
Online
1 EJA110-1
2 EJA110-2
3 EJA110-3

HELP

SET

HOME

OK

EJA:EJA110-1:
Online
1 Device setup
2 Pres 0.00 mmH2O
3 A01 Out .000 mA
4 LRV 0.00 mmH2O
5 URM 3500.00 mmH2O

DEL

SET

ABORT

OK

2

2

HART Communicator
1 Offline
2 Online
3 Transfer
4 Frequency Device
5 Utility

HELP

DEL

ABORT

OK

3

3

Example:

Communication when set in the multi-drop mode

To Release the Multi-drop Mode:

Follow the procedure below.

1. Call up the

Poll addr

display, and set the address

to 0.

2. Call up the

Auto Poll

display, and set to

No

.

(18) External Switch Mode

• Enabling/inhibiting zero point adjustment using the

external zero-adjustment screw on the transmitter.

Follow the procedure below to enable or inhibit zero

point adjustment from the zero-adjustment screw on
the transmitter.

This is set to

ENABLE

when the instrument is

shipped.

F0237.EPS

(ENTER)

EJA:
Ext SW mode
Enable
Enable
Inhibit

HELP

SEND

ESC

ENTER

Select Inhibit and press ENTER
(F4)
.
Press SEND (F2) to send the data.

(SEND)

1. Device setup

4. Detailed setup

5. Device information

1. Field device info

7. Ext SW mode

Example: Inhibiting zero adjustment by the external zero-

adjustment screw

Advertising