This manual describes the function, performance, and
operating procedures of the DPharp EJA Series with
HART protocol. The DPharp EJA Series with HART
protocol uses the same pressure sensing element as in
DPharp EJA with BRAIN protocol. Therefore, this
manual describes only the functions unique to HART
Communicator operating procedures which are not
covered in the DPharp EJA with BRAIN protocol
instruction manual. For the items listed below which
are common to both the HART protocol and BRAIN
protocol, see the applicable user’s manuals listed in
Table 1.

Contents of Individual User’s Manuals

• INTRODUCTION
• HANDLING CAUTIONS
• COMPONENT NAMES
• INSTALLATION
• INSTALLING IMPULSE PIPING
• WIRING
• OPERATION

Zero Point Adjustment

(For BRAIN Protocol)

BRAIN TERMINAL BT200 OPERATION

(For BRAIN Protocol)

• MAINTENANCE
PARAMETER SUMMARY

(For BRAIN Protocol)

• GENERAL SPECIFICATIONS

Contents of this User’s Manual for HART Protocol
—IM 01C22T01-01E—

ZERO POINT ADJUSTMENT
HART Communicator OPERATION
PARAMETER LISTS

F01.EPS

Figure 1.

Relationship between Individual Manuals and
HART Manual Contents

Table 1.

Individual User’s Manuals

EJA110A, EJA120A, EJA130A

IM 01C21B01-01E

EJA210A, EJA220A

IM 01C21C01-01E

EJA310A, EJA430A, EJA440A

IM 01C21D01-01E

EJA510A, EJA530A

IM 01C21F01-01E

EJA110, EJA120

IM 01C22B01-01E

EJA210, EJA220

IM 01C22C01-01E

EJA310, EJA430

IM 01C22D01-01E

EJA118W, EJA118N, EJA118Y

IM 01C22H01-01E

EJA438W, EJA438N

IM 01C22J01-01E

EJA115

IM 01C22K01-01E

T01.EPS

Manual No.

Model

CAUTION

Matching of communicator DD and instrument DD
Before using model 275 HART communicator,
check that the DD(Device Description) installed in
the communicator matches to that of instruments
to set up. To check the DD in the instrument or
the HART communicator, follow the steps below.
If the correct DD is not installed in the communi-
cator, you must upgrade the DD at the HART
official programming sites. For communication
tools other than Model 275 HART communicator,
contact vendors of each for upgrade information.

1. Checking the DD in the instrument

1) Connect the communicator to the instrument

to set up.

2) Call "Device setup" and press

[

]

.

3) Call "Review" and press [

].

4) By pressing [NEXT] or [PREV], find "Fld dev

rev" to show the DD of the instrument.

F02.EPS

EJA:
Review
Fld dev rev
2

HELP

PREV

NEXT

EXIT

"The instrument DD is
Version 2."

[Example]

2. Checking the DD in Model 275 HART commu-

nicator
1) Turn on the communicator alone.
2) Call "Utility" from main menu and press [

].

3) Call "Simulation" and press [

].

4) Select "YOKOGAWA" from manufacturers

list by pressing [ ]

and press [

].

5) Select the model name of the instrument(i.e.

EJA) by pressing [ ]

and press

[

]

to

show the DD of the communicator.

F03.EPS

HART Communicator
Fld dev rev
1 Dev v1, DD v2
2 Dev v2, DD v1

[Example]

"The communicator DD
supports Version 1 and 2."

Version 1 and 2.