<8. Parameter Summary>

30

IM 01C22A01-01E

BRAIN Communication Parameter List

Instruments to which applicable:

F: Differential pressure transmitters: EJA110A, EJA120A, EJA130A, EJA118W, EJA118N, EJA118Y, and EJA115

P: Pressure transmitters:

EJA310A, EJA430A, EJA440A, EJA510A, EJA530A, EJA438W, and EJA438N

L: Liquid level transmitters:

EJA210A and EJA220A

No.

Item

Description

Rewrita-

bility

Remarks

Default Value

Applicability

F

P

L

01

MODEL

Model+capsule type

02

TAG NO.

Tag number

16 alphanumerics

03

SELF CHECK

Self-diagnostic result

GOOD/ERROR

A

DISPLAY

Measured data display

Menu name

A10 OUTPUT (%)

Output (in %)

–5 to 110%*

3

A11 ENGR. OUTPUT

Output (in engineering units)

–19999 to 19999

A20 AMP TEMP

Amplifi er temperature

Unit specifi ed in D30

A21 CAPSULE TEMP

Capsule temperature

Unit specifi ed in D30

A30 STATIC PRESS

Static pressure

Unit specifi ed in D31*

1

A40 INPUT

Input (indicated as the

value after zeroing)

–32000 to 32000

A60 SELF CHECK

Self-diagnostic

messages

GOOD/ERROR, CAP MODULE FAULT, AMP

MODULE FAULT, OUT OF RANGE, OUT OF SP

RANGE*

1

, OVER TEMP (CAP),OVER TEMP

(AMP), OVER OUTPUT, OVER DISPLAY, ILLEGAL

LRV, ILLEGAL HRV, ILLEGAL SPAN, and ZERO

ADJ OVER

B

SENSOR TYPE

Sensor type

Menu name

B10 MODEL

Model+span

16 uppercase alphanumerics

B11 STYLE NO.

Style number

B20 LRL

Lower range-limit

–32000 to 32000

B21 URL

Upper range-limit

–32000 to 32000

B30 MIN SPAN

Minimum span

–32000 to 32000

B40 MAX STAT.P.

Maximum static pressure*

6

B60 SELF CHECK

Self-diagnostic 

messages

Same as A60

C

SETTING

Setting data

Menu name

C10 TAG. NO.

Tag number

16 alphanumerics

As specifi ed when

ordered.

C20 PRESS UNIT

Measurement range units

Selected from mmH

2

O,

mmAq, mmWG, mmHg,

Torr, Pa, hPa, kPa, MPa,

mbar, bar, gf/cm

2

, kgf/cm

2

,

inH

2

O, inHg, ftH

2

O, psi, or atm

As specifi ed when

ordered.

C21 LOW RANGE

Measurement range, lower

range value

–32000 to 32000(but within

measurement range)

As specifi ed when

ordered.

C22 HIGH RANGE

Measurement range,

higher range value

–32000 to 32000(but within

measurement range)

As specifi ed when

ordered.

C30 AMP DAMPING

Damping time constant

Selected from 0.2*

2

, 0.5, 1.0,

2.0, 4.0, 8.0, 16.0, 32.0, or

64.0 sec.

2.0 s

C40 OUTPUT MODE

Output mode and integral

indicator mode

Selected from OUT:LIN; DSP:

LIN, OUT:LIN; DSP:SQR,

OUT:SQR; DSP:SQR

As specifi ed when

ordered.

If not specifi ed,

OUT: LIN; DSP: LIN.

C60 SELF CHECK

Self-diagnostic messages

Same as A60

D

AUX SET 1

Auxiliary setting data 1

Menu name

D10 LOW CUT

Low cut

0.0 to 20.0%

10.0%

D11 LOW CUT MODE

Low cut mode

LINEAR/ZERO

LINEAR

D15 OUT LIMIT(L)

Lower output range-limit

–5.0 to 110.0%

–5.0%*

7

D16 OUT LIMIT(H)

Lower output range-limit

–5.0 to 110.0%

110.0%

D20 DISP SELECT

Display selection

NORMAL %/USER SET, USER

& %/INP PRES, PRES & %

As specifi ed when

ordered.

D21 DISP UNIT

Engineering unit for display

8 uppercase alphanumerics

D22 DISP LRV

Engineering range, lower

range value

–19999 to 19999

As specifi ed when

ordered.

D23 DISP HRV

Engineering range, higher

range value

–19999 to 19999

As specifi ed when

ordered.