Parameter summary – Yokogawa EJA115 User Manual

Page 33

Advertising
background image

<8. Parameter Summary>

31

IM 01C22A01-01E

No.

Item

Description

Rewrita-

bility

Remarks

Default Value

Applicability

F

P

L

D30 TEMP UNIT

Temperature setting units

deg C/deg F

deg C

D31 STAT. P. UNIT

Static pressure setting

units

Selected from mmH

2

O,

mmAq, mmWG, mmHg, Torr,

Pa, hPa, kPa, MPa, mbar,

bar, gf/cm

2

, kgf/cm

2

, inH

2

O,

inHg, ftH

2

O, psi, or atm

As specifi ed when

ordered. If not

specifi ed, MPa.

D40 REV OUTPUT

Output reversal

NORMAL/REVERSE

If not specifi ed,

NORMAL.

D45 H/L SWAP

Impulse piping accessing

direction

NORMAL/REVERSE*

4

NORMAL

D52 BURN OUT

CPU error

HIGH/LOW, –5 to 110%*

3

HIGH

D53 ERROR OUT

Hardware error

HOLD/HIGH/LOW, –5 to

110%*

3

HIGH

D60 SELF CHECK

Self-diagnostic messages

Same as A60

E

AUX SET 2

Auxiliary setting data 2

Menu name

E10 DFS MODE

DFS mode

OFF/ON*

5

ON

E14 TEMP SELECT

Reference temperature sensor

AMP. TEMP/CAP. TEMP*

5

CAP. TEMP

E15 TEMP ZERO

Zero shift conpensation setup

±610.00*

5

0.00

E30 BI DIRE MODE

Bidirectional mode

OFF/ON

OFF

E50 AUTO RECOVER Auto-recover from sensor

error

OFF/ON

ON

E60 SELF CHECK

Self-diagnostic messages

Same as A60

H

AUTO SET

Automatic setup

Menu name

H10 AUTO LRV

Automatic measurement

range lower range value setup

–32000 to 32000

Displays the same

data as C21.

H11 AUTO HRV

Automatic measurement range

higher range value setup

–32000 to 32000

Displays the same

data as C22.

H60 SELF CHECK

Self-diagnostic messages

Same as A60

J

ADJUST

Adjustment data

Menu name

J10 ZERO ADJ

Automatic zero adjustment

–5 to 110.0%*

3

J11 ZERO DEV.

Manual zero adjustment

J15 SPAN ADJ

Manual span adjustment

–10.00 to 10.00%

0.00%

J20 EXT. ZERO ADJ

External zero adjustment

screw permission

ENABLE/INHIBIT

J30 OUTPUT 4mA

4mA adjustment

–10.00 to 10.00%

0.00%

J31 OUTPUT 20mA

20mA adjustment

–10.00 to 10.00%

0.00%

J60 SELF CHECK

Self-diagnostic messages

Same as A60

K

TEST

Tests

Menu name

K10 OUTPUT in %

Test output % setting

–5 to 110.0%*

3

Displays

‘ACTIVE’ while executing

K60 SELF CHECK

Self-diagnostic messages

Same as A60

M

MEMO

Memo

Menu name

M10 MEMO 1

Memo

8 uppercase alphanumerics

M20 MEMO 2

Memo

8 uppercase alphanumerics

M30 MEMO 3

Memo

8 uppercase alphanumerics

M40 MEMO 4

Memo

8 uppercase alphanumerics

M50 MEMO 5

Memo

8 uppercase alphanumerics

M60 SELF CHECK

Self-diagnostic messages

Same as A60

P

RECORD

History of the errors

P10 ERROR REC 1

Last error

Display the error

P11 ERROR REC 2

One time before

Display the error

P12 ERROR REC 3

Two time before

Display the error

P13 ERROR REC 4

Three time before

Display the error

P60 SELF CHECK

Self-diagnostic messages

Same as A60

*1:

In case of Model EJA120A, static pressure cannot be measured. The display is always 0 MPa, but this is not a measured value.

*2:

When Optional code /F1 is specifi ed, substitute the value with 0.1.

*3:

When Optional code /F1 is specifi ed, substitute the value –5 with –2.5.

*4:

Not applicable for Model EJA115.

*5:

Applicable only for Model EJA118W, EJA118N, EJA118Y, EJA438W, and EJA438N.

*6:

See MWP(max. working pressure) on the nameplate. B40 shows an approximate value of maximum pressure for the capsule.

*7:

Unless otherwise specifi ed by order. When Optional code /F1 is specifi ed, substitute the value –5 with –2.5.

Parameter Summary

8