<5. Wiring>

23

IM 01C22A01-01E

5. Wiring

NOTE

For F

OUNDATION

Fieldbus and PROFIBUS PA

communication types, please refer to manuals in the
attached CD-ROM.

5.1 Wiring

Precautions

IMPORTANT

• Lay wiring as far as possible from electrical noise

sources such as large capacity transformers,
motors, and power supplies.

• Remove electrical connection dust cap before

wiring.

• All threaded parts must be treated with

waterproofi ng sealant. (A non-hardening silicone
group sealant is recommended.)

• To prevent noise pickup, do not pass signal and

power cables through the same ducts.

• Explosion-protected instruments must be wired

in accordance with specifi c requirements (and,
in certain countries, legal regulations) in order
to preserve the effectiveness of their explosion-
protected features.

• The terminal box cover is locked by an Allen head

bolt (a shrouding bolt) on CENELEC and IECEx
fl

ameproof type transmitters. When the shrouding

bolt is driven clockwise by an Allen wrench, it is
going in and cover lock is released, and then the
cover can be opened by hand.
When a cover is closed it should be locked by a
shrouding bolt without fail. Tighten the shrouding
bolt to a torque of 0.7 N·m.

Shrouding Bolt

Shrouding Bolt

F0501.ai

5.2 Connections of External

Wiring to Terminal Box

5.2.1 Power Supply Wiring Connection

Connect the power supply wiring to the SUPPLY + and
– terminals.

Power supply

+

Transmitter terminal box

F0502.ai

Figure 5.1

Power Supply Wiring Connection

5.2.2 Handheld Terminal Connection

Connect the handheld terminal to the SUPPLY + and
– terminals (Use hooks). Communication line requires a
reception resistor of 250 to 600

Ω in series.

Transmitter terminal box

BT200 etc.

F0503.ai

Power supply

+

Ignore the polarity
since it is AC-coupled
to the terminal box.

250 to 600

Ω

Figure 5.2

Handheld Terminal Connection

5.3 Wiring

CAUTION

For the intrinsically safe equipment and fl ameproof
equipment, wiring materials and wiring work for these
equipment including peripherals are strictly restricted.
Users absolutely must read “Installation and Operating
Precautions for TIIS Intrinsically Safe Equipment”
and “Installation and Operating Precautions for TIIS
Flameproof Equipment” at the end of this manual prior
to the work.

W

iring

5