<5. Wiring>

25

IM 01C22A01-01E

2) Insert the cable through the union cover, the union

coupling, the clamp nut, the clamp ring, the gland,
the washer, the rubber packing, and the packing
box, in that order.

3) Insert the end of the cable into the terminal box.
4) Tighten the union cover to grip the cable. When

tightening the union cover, tighten approximately
one turn past the point where the cable will no
longer move up and down.
Proper tightening is important. If it is too tight, a
circuit break in the cable may occur; if not tight
enough, the fl ameproof effectiveness will be
compromised.

5) Fasten the cable by tightening the clamp nut.
6) Tighten the lock nut on the union cover.
7) Connect the cable wires to each terminal.

O-ring

Adapter body

Lock nut

Wrench

Packing box

Rubber packing

Washer

Gland

Clamp ring

Clamp nut

Union coupling

Lock nut

Wrench

Union cover

Cable

Apply a non-hardnening
sealant to the threads for
waterproofing.

F0508.ai

Figure 5.7

Installing Flameproof Packing Adapter

Flameproof metal conduit wiring

• A

seal

fi

tting must be installed near the terminal box

connection port for a sealed construction.

• Apply a non-hardening sealant to the threads of the

terminal box connection port, fl exible metal conduit
and seal fi tting for waterproofi ng.

F0509.EPS

Non-hazardous area

Hazardous area

Flameproof
heavy-gauge
steel conduit

Tee

Drain plug

Seal fitting

Gas sealing device

Flameproof flexible
metal conduit

Apply a non-hardening
sealant to the threads
of these fittings for
waterproofing

After wiring, impregnate the fitting
with a compound to seal tubing.

Figure 5.8

Typical Wiring Using Flameproof Metal
Conduit

5.4 Grounding

Grounding is always required for the proper operation of
transmitters. Follow the domestic electrical requirements
as regulated in each country. For a transmitter with builtin
lightning protector, grounding should satisfy ground
resistance of 10

Ω or less.

Ground terminals are located on the inside and outside of
the terminal box. Either of these terminals may be used.

WARNING

For TIIS fl ameproof type and intrinsically safe,
grounding should satisfy Class D requirements
(grounding resistance, 100

Ω or less).

Ground terminal
(Inside)

Ground terminal
(Outside)

Transmitter terminal box

F0610.ai

Figure 5.9

Ground Terminals

5.5 Power Supply Voltage and

Load Resistance

When confi guring the loop, make sure that the external
load resistance is within the range in the fi gure below.

(Note)

In case of an intrinsically safe transmitter, external load
resistance includes safety barrier resistance.

600

250

0

10.5

16.4

24.7

42

External

load

resistance

R (

Ω)

Power supply voltage E (V DC)

F0511.ai

Communication

applicable range

BRAIN and HART

R=

E–10.5

0.0236

Figure 5.10

Relationship between Power Supply
Voltage and External Load Resistance