3. ABOUT FIELDBUS

3.

ABOUT FIELDBUS

3.1 Outline

Fieldbus is a bi-directional digital communication
protocol for field devices, which offers an advancement in
implementation technologies for process control systems
and is widely employed by numerous field devices.

EJA Series Fieldbus communication type employs the
specification standardized by The Fieldbus Foundation,
and provides interoperability between Yokogawa
devices and those produced by other manufacturers.
Fieldbus comes with software consisting of two AI
function blocks, providing the means to implement a
flexible instrumentation system.

For information on other features, engineering, design,
construction work, startup and maintenance of
Fieldbus, refer to “Fieldbus Technical Information” (TI
38K03A01-01E).

3.2 Internal Structure of EJA

The EJA contains two virtual field devices (VFD) that
share the following functions.

3.2.1 System/network Management VFD

• Sets node addresses and Phisical Device tags (PD

Tag) necessary for communication.

• Controls the execution of function blocks.
• Manages operation parameters and communication

resources (Virtual Communication Relationship:
VCR).

3.2.2 Function Block VFD

(1)Resource block

• Manages the status of EJA hardware.
• Automatically informs the host of any detected

faults or other problems.

(2)Transducer block

• Converts sensor output to pressure signals and

transfers to AI function block.

(3)AI1 function block

• Conditions raw data from the Transducer block.
• Outputs differential pressure signals.
• Carries out scaling, damping and square root

extraction.

(4)AI2 function block

• Outputs static pressure signals.

(5)PID function block

• Performs the PID control computation based on the

deviation of the measured value from the setpoint.

3.3 Logical Structure of Each

Block

F0301.EPS

EJA
Fieldbus

System/network management VFD

Function block VFD

Link Master (option)

PD Tag

Sensor

input

Resource block

Block tag

Parameters

PID function

block (option)

Communication

parameters

VCR

Node address

Function block

execution schedule

AI function

block

Output

AI function

block

Block tag

OUT

Parameters

Transducer

block

Block tag

Parameters

Sensor

Figure 3.1 Logical Structure of Each Block

Setting of various parameters, node addresses, and PD
Tags shown in Figure 3.1 is required before starting
operation.

3.4 Wiring System Configuration

The number of devices that can be connected to a
single bus and the cable length vary depending on
system design. When constructing systems, both the
basic and overall design must be carefully considered
to achieve optimal performance.