4.2 Host Setting

To activate Fieldbus, the following settings are
required for the host.

IMPORTANT

Do not turn off the power immediately after
setting. When the parameters are saved to the
EEPROM, the redundant processing is executed
for an improvement of reliability. If the power is
turned off within 60 seconds after setting is
made, the modified parameters are not saved
and the settings may return to the original
values.

Table 4.1 Operation Parameters

T0401.EPS

Symbol

Parameter

Description and Settings

Minimum value of
communication data
intervals. Unit of time is in
octets (256

µ

s). Set the

maximum specification for
all devices. For EJA, set a
value of 4 or greater.

Indicates the time
necessary for immediate
reply of thje device. Unit of
time is in octets (256

µ

s).

Set maximum specification
for all devices. For EJA,
set a value of 4 or greater.

Slot-Time

V (ST)

First-Unpolled-Node

Minimum-Inter-PDU-
Delay

Maximum-Reply-
Delay

Unused address range.

Indicate the address next
to the address range used
by the host. Set 0x15 or
greater.

Number-of-
consecutive-
Unpolled-Node

The worst case time
elapsed until a reply is
recorded. The unit is Slot-
time; set the value so that
V (MRD)

ϫ

V (ST) is the

maximum value of the
specification for all
devices. For EJA, the
setting must be a value of
12 or greater.

V (MRD)

V (MID)

V (FUN)

V (NUN)

Not used

0x00

0xF7

0xF8

0x0F

0x10

0x13

0x14

0xFB

0xFC

0xFF

V(FUN)

V(FUN)

ϩ

V(NUN)

LM device

Bridge device

Unused

V(NUN)

Note 1: Bridge device: A linking device which brings data from one

or more H1 networks.

Note 2: LM device: with bus control function (Link Master function)
Note 3: BASIC device: without bus control function

BASIC device

Default address

Portable device address

F0402.EPS

Figure 4.2 Available Address Range