3 definition of combining function blocks, Definition of combining function blocks -2 – Yokogawa EJA115 User Manual

Page 24

Advertising
background image

IM 01C22T02-01E

5-2

5. CONFIGURATION

range of the BASIC device. When the EJA is used as
Link Master, place the EJA in the range of LM device.
Set the range of addresses to be used to the LM device.
Set the following parameters.

Table 5.1

Parameters for Setting Address Range

T0501.EPS

V (FUN) First-Unpolled-Node

Indicates the address next
to the address range used
for the host or other LM
device.

V (NUN) Number-of-

consecutive-
Unpolled-Node

Unused address range

Symbol

Parameters

Description

The devices within the address range written as
“Unused” in Figure 5.1 cannot be used on a Fieldbus.
For other address ranges, the range is periodically
checked to identify when a new device is mounted.
Care must be taken to keep the unused device range as
narrow as possible so as to lessen the load on the
Fieldbus.

0xF7

0xF8

0xFB

0xFC

0xFF

V(FUN)

V(FUN)

ϩ

V(NUN)

LM device

Unused

V(NUN)

BASIC device

Default address

Portable device address

F0501.EPS

Not used

0x00

0x0F

0x10

0x13

0x14

Bridge device

Figure 5.1 Available Range of Node Addresses

To ensure stable operation of Fieldbus, determine the
operation parameters and set them to the LM devices.
While the parameters in Table 5.2 are to be set, the
worst-case value of all the devices to be connected to
the same Fieldbus must be used. Refer to the specifica-
tion of each device for details. Table 5.2 lists EJA
specification values.

Table 5.2

Operation Parameter Values of the EJA to be
Set to LM Devices

Indicates the time
necessary for immediate
reply of thje device. Unit of
time is in octets (256

µ

s).

Set maximum specification
for all devices. For EJA,
set a value of 4 or greater.

T0502.EPS

Symbol

Parameters

Description and Settings

V (ST)

Slot-Time

V (MID) Minimum-Inter-PDU-

Delay

Minimum value of
communication data
intervals. Unit of time is in
octets (256

µ

s). Set the

maximum specification for
all devices. For EJA, set a
value of 4 or greater.

V (MRD) Maximum-Response-

Delay

The worst case time
elapsed until a reply is
recorded. The unit is Slot-
time; set the value so that
V (MRD)

ϫ

V (ST) is the

maximum value of the
specification for all
devices. For EJA, the
setting must be a value of
12 or greater.

5.3 Definition of Combining

Function Blocks

The input/output parameters for function blocks are
combined. For the EJA, two AI blocks output param-
eter (OUT) and PID block are subject to combination.
They are combined with the input of the control block
as necessary. Practically, setting is written to the EJA
link object with reference to “Block setting” in Section
5.6 for details. It is also possible to read values from
the host at proper intervals instead of connecting the
EJA block output to other blocks.

The combined blocks need to be executed synchro-
nously with other blocks on the communications
schedule. In this case, change the EJA schedule
according to the following table. The values in the
table are factory-settings.

Table 5.3 Execution Schedule of the EJA Function Blocks

T0503.EPS

Index

Parameters

Setting (Enclosed is

factory-setting)

269

(SM)

MACROCYCLE_
DURATION

Cycle (MACROCYCLE)
period of control or
measurement. Unit is 1/32
ms. (16000 = 0.5 s)

276

(SM)

FB_START_ENTRY.1 AI1 block startup time.

Elapsed time from the start
of MACROCYCLE specified
in 1/32 ms. (0 = 0 s)

277

(SM)

FB_START_ENTRY.2

278

(SM)

FB_START_ENTRY.3

279

(SM)

FB_START_ENTRY.4

AI2 block startup time.
Elapsed time from the start
of MACROCYCLE specified
in 1/32 ms. (8000 = 0.25 s)

Not used.

Not used.