4 setting of tags and addresses, Setting of tags and addresses -3 – Yokogawa EJA115 User Manual

Page 25

Advertising
background image

IM 01C22T02-01E

5-3

5. CONFIGURATION

A maximum of 100 ms is taken for execution of AI
block. For scheduling of communications for combina-
tion with the next function block, the execution is so
arranged as to start after a lapse of longer than 100 ms.
In no case should two AI function blocks of the EJA
be executed at the same time (execution time is
overlapped).

Figure 5.3 shows an example of schedule based on the
loop shown in Figure 5.2.

F0502.EPS

LIC100

FIC100

FC100

FI100

EJA

#2

LI100

EJA

#1

Figure 5.2 Example of Loop Connecting Function Block of

Two EJA with Other Instruments

LI100

LIC100

FIC100

FC100

FI100

Commu-

nication

Schedule

OUT

IN

OUT

CAS_IN

BKCAL_OUT

BKCAL_IN

BKCAL_IN

BKCAL_OUT

IN

Unscheduled

Communication

Scheduled
Communication

F0503.EPS

Macrocycle (Control Period)

Figure 5.3 Function Block Schedule and Communication

Schedule

When the control period (macrocycle) is set to more
than 4 seconds, set the following interval to be more
than 1% of the control period.

- Interval between “end of block execution” and “start

of sending CD from LAS”

- Interval between “end of block execution” and “start

of the next block execution”

5.4 Setting of Tags and

Addresses

This section describes the steps in the procedure to set
PD Tags and node addresses in the EJA. There are
three states of Fieldbus devices as shown in Figure 5.4,
and if the state is other than the lowest
SM_OPERATIONAL state, no function block is
executed. EJA must be transferred to this state when an
EJA tag or address is changed.

UNINITIALIZED

(No tag nor address is set)

Tag clear

Tag setting

INITIALIZED

(Only tag is set)

SM_OPERATIONAL

(Tag and address are retained, and
the function block can be executed.)

Address clear

F0504.EPS

Address setting

Figure 5.4 Status Transition by Setting PD Tag and Node

Address

EJA has a PD Tag (PT1001) and node address (245, or
hexadecimal F5) that are set upon shipment from the
factory unless otherwise specified. To change only the
node address, clear the address once and then set a new
node address. To set the PD Tag, first clear the node
address and clear the PD Tag, then set the PD Tag and
node address again.

Devices whose node address have been cleared will
have the default address (randomly chosen from a
range of 248 to 251, or from hexadecimal F8 to FB).
At the same time, it is necessary to specify the device
ID in order to correctly specify the device. The device
ID of the EJA is 5945430003xxxxxxxx. (The
xxxxxxxx at the end of the above device ID is a total
of 8 alphanumeric characters.)