4 function block parameters, Function block parameters -8 – Yokogawa EJA115 User Manual

Page 30

Advertising
background image

IM 01C22T02-01E

5-8

5. CONFIGURATION

Table 5.13 View Object for AI1.AI2 Function Block

T0513.EPS

1

ST_REV

2

2

TAG_DESC

3

STRATEGY

4

ALERT_KEY

5

MODE_BLK

4

6

BLOCK_ERR

2

7

PV

8

OUT

5

9

SIMULATE

10

XD_SCALE

11

OUT_SCALE

12

GRANT_DENY

13

IO_OPTS

14

STATUS_OPTS

15

CHANNEL

16

L_TYPE

17

LOW_CUT

18

PV_FTIME

5

19

FIELD_VAL

20

UPDATE_EVT

21

BLOCK_ALM

8

22

ALARM_SUM

23

ACK_OPTION

24

ALARM_HYS

25

HI_HI_PRI

26

HI_HI_LIM

27

HI_PRI

28

HI_LIM

29

LO_PRI

30

LO_LIM

31

LO_LO_PRI

32

LO_LO_LIM

33

HI_HI_ALM

34

HI_ALM

35

LO_ALM

36

LO_LO_ALM

2

11

11

2

2

4

2

5

5

5

5

8

2

2

1

31

26

31

46

2

2

2

1

4

4

2

4

1

4

1

4

1

4

1

4

VIEW

1

VIEW

2

VIEW

3

VIEW

4

Relative

Index

Parameter Mnemonic

Totals (# bytes)

Table 5.14 Indexes of View for Each Block

T0514.EPS

VIEW_3

VIEW_2

VIEW_1

Resourse Block

Transducer Block

AI1 Function Block

AI2 Function Block

(PID Function Block)

VIEW_4

40100

40200

40400

40410

40800

40101

40201

40401

40411

40801

40102

40202

40402

40412

40802

40103

40203

40403

40413

40803

5.6.4 Function Block Parameters

Function block parameters can be read from the host or
can be set. For a list of the parameters of blocks held
by the EJA, refer to “List of parameters for each block
of the EJA” in Appendix 1. For PID/LM function
option, refer to Appendix 4&5. The following is a list
of important parameters with a guide to how to set
them.

MODE_BLK:

Indicates the three types of function block modes;
Out_Of_Service, Manual, and Auto. In
Out_Of_Service mode, the AI block does not
operate. The Manual mode does not allow values to
be updated. The Auto mode causes the measured
value to be updated. Under normal circumstances,
set the Auto mode to take effect. The Auto mode is
the factory default.

CHANNEL:

This is the parameter of the transducer block to be
input to the AI block. AI1 block is assigned differ-
ential pressure and AI2 block is assigned static
pressure, respectively. Do not change this setting.

XD_SCALE:

Scale of input from the transducer block. The
calibrated range is factory set (from 0% point to
100% point). Usually, the unit is set in kPa. Chang-
ing the unit (can be set only in pressure unit) also
causes the unit within the transducer block to be
automatically changed. (The unit is automatically
changed according to the unit selected by AI1.) Unit
index which can be set by XD_SCALE is as shown
below.

Table 5.15 Unit Index by XD_SCALE

T0515.EPS

MPa

kPa

hPa

bar

mbar

atm

1132, 1545 (abs), 1546 (gauge)

1133, 1547 (abs), 1548 (gauge)

1136, 1553 (abs), 1554 (gauge)

1137

1138

1140

L_TYPE:

Specifies the operation function of the AI block. If
set to “Direct”, the input delivered to CHANNEL is
directly reflected on OUT. If set to “Indirect”,
scaling by XD_SCALE and OUT_SCALE is carried
out and is reflected on OUT. If set to “Indirect
SQRT”, after scaling by XD_SCALE, the square
root is extracted and the value scaled by
OUT_SCALE is reflected on OUT.

Advertising
This manual is related to the following products: