IM 01C22T02-01E

5-9

5. CONFIGURATION

PV_FTIME:

Sets the time constant of the damping function
within AI block (primary delay) in seconds.

OUT_SCALE:

Sets the range of output (from 0% to 100%). The
unit can also be set with ease.

Alarm Priority:

Indicates the priority of the process alarm. If a value
of 3 or greater is set, an alarm is transmitted. The
factory default is 0. Four types of alarm can be set:
HI_PRI, HI_HI_PRI, LO_PRI, and LO_LO_PRI.

Alarm Threshold:

Sets the threshold at which a process alarm is
generated. The factory default setting is a value that
does not generate an alarm. Four types of alarm can
be set: HI_LIM, HI_HI_LIM, LO_LIM, and
LO_LO_LIM.

5.6.5 Transducer Block Parameters

The transducer block sets functions specific to the
measurement of the differential and normal pressure of
the EJA. For a list of the parameters of each block of
the EJA, refer to “List of parameters for each block of
the EJA” in Appendix 1. The following is a list of
important parameters with a guide to how to set them.

TERTIARY_VALUE:

Displays the capsule temperature of the EJA.

TERTIARY_VALUE_UNIT:

Sets display unit of temperature at EJA. If set to
1001,

°

C is used, and if set to 1002,

°

F is used. The

factory default setting is

°

C.

DISPLAY_MODE:

Sets the unit to be used for LCD display.
1. Engineering Unit (Engr. Unit)
2. %
3. 1/10 @ Engr. Unit
4. 1/100 @ Engr. Unit
5. 1/1000 @ Engr. Unit
6. 1/10000 @ Engr. Unit
7. 1/1000000 @ Engr. Unit

DISPLAY_CYCLE:

Sets the cycle of LCD display in units of function
block execution cycles. The factory default setting is
1, but if a low temperature environment makes it
difficult to view the display, it is recommended that
you set a longer display cycle.