6. IN-PROCESS OPERATION

Update Alerts (Generated when a important

(restorable) parameter is updated)

By Resource Block

Update Event

By Transducer Block Update Event
By AI1 Block

Update Event

By AI2 Block

Update Event

By PID Block

Update Event

An alert has following structure:

Table 6.2 Alert Object

T0602.EPS

Parameter

Name

Explanation

1

Block Index

Index of block from which
alert is generated

2

Alert Key

Alert Key copied from the
block

3

Standard
Type

Type of the alert

4

Mfr Type

Alert Name identified by
manufacturer specific DD

5

1

2

3

4

5

Message
Type

Reason of alert notification

1

2

3

6

Priority

Priority of the alarm

7

Time Stamp

Time when this alert is first
detected

6

7

6

7

8

Subcode

Enumerated cause of this
alert

9

Value

Value of referenced data

8

9

10

Relative
Index

Relative index of referenced
data

Static
Revision

Value of static revision
(ST_REV) of the block

10

8

11

Unit Index

Unit code of referenced data

11

9

4

5

Subindex

Analog

Alert

Discrete

Alert

Update

Alert

6.3 Simulation Function

The simulation function simulates the input of a
function block and lets it operate as if the data was
received from the transducer block. It is possible to
conduct testing for the downstream function blocks or
alarm processes.

A SIMULATE_ENABLE switch is mounted in the
EJA amplifier. This is to prevent the accidental
operation of this function. When this is switched on,
simulation is enabled. (See Figure 6.2.) To initiate the
same action from a remote terminal, if REMOTE
LOOP TEST SWITCH is written to the
SIM_ENABLE_MSG parameter (index 1044) of the
resource block, the resulting action is the same as is
taken when the above switch is on. Note that this
parameter value is lost when the power is turned OFF.

In simulation enabled status, an alarm is generated
from the resource block, and other device alarms will
be masked; for this reason the simulation must be
disabled immediately after using this function.

The SIMULATE parameter of AI block consists of the
elements listed in Table 6.3 below.

Table 6.3

SIMULATE Parameter

T0603.EPS

Sub-

index

Parameters

Description

1

Simulate Status

Sets the data status to be
simulated.

2

Simulate Value

Sets the value of the data
to be simulated.

3

Transducer Status

Displays the data status
from the transducer block.
It cannot be changed.

4

Transducer Value

Displays the data value
from the transducer block.
It cannot be changed.

5

Simulate En/Disable

Controls the simulation
function of this block.
1: Simulation disabled
(standard)
2: Simulation started

When Simulate En/Disable in Table 6.3 above is set to
2, the applicable function block uses the simulation
value set in this parameter instead of the data from the
transducer block. This setting can be used for propaga-
tion of the status to the trailing blocks, generation of a
process alarm, and as an operation test for trailing
blocks.

F0602.EPS

Amplifier Assembly

1

2

O

N

"OFF" during operation

Not in use

SIM. ENABLE

Figure 6.2 SIMULATE_ENABLE Switch Position