8. GENERAL SPECIFICATIONS

8.

GENERAL SPECIFICATIONS

8.1 Standard Specifications

For items other than those described below, refer to

each User’s Manual.

Applicable Model:

All DPharp EJA series

Output Signal:

Digital communication signal based on F

OUNDATION

fieldbus protocol.

Supply Voltage

9 to 32 V DC for general use, flameproof type, and

nonincendive type

9 to 24 V DC for intrinsically safe type Entity model

9 to 17.5 V DC for intrinsically safe type FISCO model

Conditions of Communication Line:

Supply Voltage: 9 to 32 V DC

Current Draw:

Steady state: 16.5 mA (max)

Software download state: 40.5 mA (max)

Power Supply Effect:

No effect (within the supply voltage of 9 to 32 V DC)

External Zero Adjustment:

External zero is continuously adjustable with 0.01%

incremental resolution of max span.

Functional Specifications:

Functional specifications for Fieldbus communication

conform to the standard specifications (H1) of F

OUNDATION

fieldbus.

Function Block: Two AI function blocks

*1

One PID function block (option)

Link Master function (option)

*1: Contact Yokogawa sales representative for the use of

function block for static pressure.

EMC Conformity Standards“

”:

,

EN61326-1 Class A, Table 2 (For use in industrial

lications)

EN61326-2-3

< Safety Barrier for CENELEC ATEX (KEMA) Intrinsically Safe Type >

T0802.EPS

Supplier

P+F

Type

Isolator

Model

KLD2-PR-Ex1. IEC1 (FISCO)

< Settings When Shipped >

T0803.EPS

Tag Number (Tag plate)

Output Mode (L_TYPE)

‘Direct’ unless otherwise specified in order

Operation Functional Class (When /LC1 is specified)

‘BASIC’ unless otherwise specified in order

‘0 to 100%’ unless otherwise specified

Damping Time Constant (PV_FTIME)

‘2 sec.’

Calibration Range (XD_SCALE) Lower/Higher Range Value

As specified in order

As specified in order *

2

Software Tag (PD tag)

‘PT1001’ unless otherwise specified in older *

3

Unit (CAL_UNIT) of Calibration Range

Selected from mmH

2

O, inH

2

O, mmHg, inHg, Pa, hPa, kPa,

MPa, g/cm

2

, kg/cm

2

, bar, mbar, psi, torr,atm

(Only one unit can be specified.)

Output Scale (OUT_SCALE) Lower/Higher Range Value

Unit of Output Scale (OUT_SCALE)

As specified in order

Node Address

‘0xF5’ unless otherwise specified in order

*2: Specified Tag Number is engraved on the stainless steel plate: Up to 16 letters using any of alphanumerics and symbols of [-], [.], and [/].
*3: Specified Software Tag is entered in the amplifier memory: Up to 32 letters using any of alphanumerics and symbols of [-] and [.].