A1.3 transducer block – Yokogawa EJA115 User Manual

Page 43

Advertising
background image

IM 01C22T02-01E

A-5

APPENDIX 1. LIST OF PARAMETERS FOR EACH BLOCK OF THE EJA

A1.3 Transducer Block

Relative

Index

Index

Explanation

Write Mode

Factory Default

Parameter Name

0

2000

TAG: “TB”

Block Header

Information on this block such as Block Tag, DD
Revision, Execution Time etc.

Block Tag
= O/S

1

2001

ST_REV

The revision level of the static data associated with the
function block. The revision value will be incremented
each time a static parameter value in the block is
changed.

2

2002

(blank)

TAG_DESC

The user description of the intended application of the
block

AUTO

3

2003

1

STRATEGY

The strategy field can be used to identify grouping of
blocks. This data is not checked or processed by the
block.

AUTO

4

2004

1

ALERT_KEY

The identification number of the plant unit. This
information may be used in the host for sorting alarms,
etc.

AUTO

5

2005

AUTO

MODE_BLK

The actual, target, permitted, and normal modes of the
block.

AUTO

6

2006

BLOCK_ERR

This parameter reflects the error status associated with
hardware or software components associated with a
block. It is a bit string, so that multiple errors may be
shown.

7

2007

UPDATE_EVT

This alert is generated by any change to the static data.

8

2008

BLOCK_ALM

The block alarm is used for all configuration, hardware,
connection failure or system problems in the block. The
cause of the alert is entered in the subcode field. The
first alert to become active will set the Active status in
the Status attribute.

9

2009

TRANSDUCER_
DIRECTORY

A directory that specifies the number and starting
indices of the transducers.

10

2010

100 (Standard Pre-
ssure with Calibration)

TRANSDUCER_
TYPE

Identifies transducer.

11

2011

XD_ERROR

The error code in transducer.

0=No failure
20=Electronics failure
22=I/O failure
21=Mechanical failure

12

2012

COLLECTION_
DIRECTORY

A directory that specifies the number, starting indices,
and DD Item Ids of the data collections in each
transducer within a transducer block.

13

2013

107: differential
pressure
108: gauge pressure
109: absolute pressure

PRIMARY_
VALUE_TYPE

The type of measurement represented by primary
value.
Followings are available for EJA:

107=differential pressure
108=gauge pressure
109=absolute pressure

O/S

14

2014

PRIMARY_
VALUE

The measured value and status available to the function
block.

15

2015

Range of capsule

PRIMARY_
VALUE_RANGE

The High and Low range limit values, engineering units
code and the number of digits to the right of the decimal
point to be used to display the primary value.

18

2018

Minimum span of
capsule

CAL_MIN_SPAN

The minimum calibration span value allowed.

16

2016

Max range

CAL_POINT_HI

The highest calibrated value.

O/S

17

2017

0

CAL_POINT_LO

The lowest calibrated value.

O/S

21

2021

Range of capsule

SENSOR_RANGE

TA0103-1.EPS

The High and Low range limit values, engineering units
code and the number of digits to the right of the decimal
point for the sensor.

19

2019

kPa

CAL_UNIT

The engineering unit for the calibrated values.

20

2020

Silicon resonant

SENSOR_TYPE

The type of sensor.

Advertising
This manual is related to the following products: