A-12

APPENDIX 3. OPERATION OF EACH PARAMETER IN FAILURE MODE

APPENDIX 3. OPERATION OF EACH

PARAMETER IN FAILURE MODE

• Following table summarizes the value of EJA parameters when LCD display indicates an Alarm.

(1)

Cause of Alarm

Capsule Module Failure

AL. 01

ALARM Display

AMP Module Failure 1

BLOCK_ERR=Input
Failure

XD_ERROR=
Mechanical Failure

PV. STATUS=BAD:
Sensor Failure

SV. STATUS=BAD:
Sensor Failure

PV. STATUS=BAD:
Sensor Failure

OUT. STATUS=BAD:
Sensor Failure

PV. STATUS=BAD:
Non Specific

OUT. STATUS=BAD:
Non Specific

PV. STATUS=BAD:
Device Failure

OUT. STATUS=BAD:
Device Failure

PV. STATUS=BAD:
Device Failure

PV. STATUS=BAD:
Non Specific

SV. STATUS=BAD:
Device Failure

BLOCK_ERR=Device
Needs Maintenance Now

XD_ERROR=I/O
Failure or Electronics Failure

SV. STATUS=BAD:
Non Specific

SV. STATUS=BAD:
Out Of Service

BLOCK_ERR=Out Of
Service

PV. STATUS=BAD:
Out Of Service

AL. 02

AMP Module Failure 2

PV. STATUS=BAD:
Non Specific

AL. 03

BLOCK_ERR=Lost
Static Data or
Lost NV Data

SV. STATUS=BAD:
Non Specific

PV. STATUS=HOLD

BLOCK_ERR=Out of
Service

OUT. STATUS=BAD:
Out of Service

PV. STATUS=BAD:
Non Specific

OUT. STATUS=BAD:
Non Specific

Resource Block is in O/S
mode

AL. 21

BLOCK_ERR=Out of
Service

Transducer Block is in
O/S mode

AL. 22

TA0301-1.EPS

PV. STATUS=HOLD

OUT. STATUS=HOLD

AI1 Block is
not scheduled

AL. 20

Resource Block

Transducer Block