Appendix 4. pid block, A4.1 function diagram, A4.2 functions of pid bock – Yokogawa EJA115 User Manual

Page 52

Advertising
background image

IM 01C22T02-01E

A-14

APPENDIX 4. PID Block

APPENDIX 4. PID BLOCK

A PID block performs the PID control computation based on the deviation of the measured value (PV) from the
setpoint (SV), and is generally used for constant-setpoint and cascaded-setpoint control.

A4.1 Function Diagram

The figure below depicts the function diagram of a PID block.

Setpoint

Output

Bypass

Input Filter

PID Control

Computation

Alarm

Processing

Mode Control

Feed-forward

Data Status

Management

Output Tracking

CAS_IN

BKCAL_OUT

RCAS_OUT

BKCAL_IN

ROUT_IN

ROUT_OUT

FF_VAL

RCAS_IN

TRK_IN_D

TRK_VAL

IN

OUT

PV

SP

FA0401.EPS

A4.2 Functions of PID Bock

The table below shows the functions provided in a PID block.

PID control computation

Control output

Switching of direction of
control action

Control action bypass

Feed-forward

Measured-value tracking

Setpoint limiters

External-output tracking

Mode change

Bumpless transfer

Initialization and manual
fallback

Manual fallback

Auto fallback

Mode shedding upon
computer failure

Alarm processing

Function

Description

Computes the control output in accordance with the PID control algorithm.

Converts the change in control output

MV to the manipulated value MV that is to be actually output.

Switches over the direction of control action between direct and reverse, i.e., the direction of changes in
the control output depending on the changes in the deviation.

When the bypass is on, the value of the SP is scaled to the range of the OUT and output as the OUT.

Adds the value of the FF_VAL (input to the PID block) to the output from the PID computation.

Equalizes the setpoint SP to the measured value PV.

Limit the value of setpoint SP within the preset upper and lower levels as well as limit the rate of change
when the PID block is in Auto mode.

Performs the scaling of the value of TRK_VAL to the range of the OUT and outputs it as the OUT.

Changes the block mode between 8 modes: O/S, IMan, LO, Man, Auto, Cas, RCas, ROut.

Prevents a sudden change in the control output OUT at changes in block mode and at switching of the
connection from the control output OUT to the cascaded secondary function block.

Changes the block mode to IMan and suspends the control action when the specified condition is met.

Changes the block mode to Man and aborts the control action.

Changes the block mode to Auto when it is Cas, and continues the control action with the setpoint set
by the operator.

Changes the block mode in accordance with the SHED_OPT setting upon a computer failure.

Generates block alarms and process alarms, and performs event updates.

TA0401.EPS

Advertising
This manual is related to the following products: