A4.17 mode shedding upon computer failure, A4.17.1 shed_opt, A4.18 alarms – Yokogawa EJA115 User Manual

Page 59: A4.18.1 block alarm (block_alm), A4.18.2 process alarms, A4.17 mode shedding upon com- puter failure, A-21, 2 only when auto is set as permitted mode

Advertising
background image

IM 01C22T02-01E

A-21

APPENDIX 4. PID Block

A4.17 Mode Shedding upon Com-

puter Failure

When the data status of RCAS_IN or ROUT_IN,
which is the setting received from a computer as the
setpoint SP, falls to Bad while the PID block is
running in the RCas or ROut mode, the mode shedding
occurs in accordance with the settings in SHED_OPT.
If the RCAS_IN data is not renewed within the time
specified by SHED_RCAS in resource block, the data
status of RCAS_IN falls to Bad.

A4.17.1 SHED_OPT

The SHED_OPT setting stipulates the specifications of
mode shedding as shown below. Only one can be set.

Available Setting

for SHED_OPT

Actions upon Computer Failure

Sets MODE_BLK.actual to Cas*

1

,

and leaves MODE_BLK.target unchanged.

Sets both MODE_BLK.actual and
MODE_BLK.target to Cas*

1

.

Sets MODE_BLK.actual to Auto*

2

, and

leaves MODE_BLK.target unchanged.

Sets both MODE_BLK.actual and
MODE_BLK.target to Auto*

2

.

Sets MODE_BLK.actual to Man, and
leaves MODE_BLK.target unchanged.

Sets both MODE_BLK.actual and
MODE_BLK.target to Man.

If Cas is in MODE_BLK.target, sets
MODE_BLK.actual to Cas*

1

, and leaves

MODE_BLK.target unchanged.
If Cas is not set in MODE_BLK.target,
sets MODE_BLK.actual to Auto*

2

, and

leaves MODE_BLK.target unchanged.

If Cas is set in MODE_BLK.target, sets
both MODE_BLK.actual and
MODE_BLK.target to Cas*

1

.

If Cas is not set in MODE_BLK.target,
sets MODE_BLK.actual to Auto*

2

, and

MODE_BLK.target to Cas.

Normal shed,
normal return

Normal shed,
no return

Shed to Auto,
normal return

Shed to Auto,
no return

Shed to Manual,
normal return

Shed to Manual,
no return

Shed to retained
target, normal
return


Shed to retained
target, no return

TA0410.EPS

*1 The modes to which a PID block can transfer are

limited to those set in MODE_BLK.permitted, and
the priority levels of modes are as shown below.
In fact, if Normal shed, normal return is set for
SHED_OPT, detection of a computer failure
causes MODE_BLK.actual to change to Cas, Auto,
or MAN, whichever is set in MODE_BLK.
permitted and has the lowest priority level.

FA0405.EPS

Higher priority
level

Lower priority
level

ROut

RCas

Cas

Auto

Man

*2 Only when Auto is set as permitted mode.

NOTE: If a control block is connected as a cascade primary block of

the PID block in question, a mode transition of the PID block
to Cas occurs in the following sequence due to initialization
of the cascade connection: RCas or ROut

Auto

Cas.

A4.18 Alarms

There are two kinds of alarms generated by a PID
block: block and process alarms.

A4.18.1 Block Alarm (BLOCK_ALM)

The block alarm BLOCK_ALM is generated upon
occurrence of either of the following errors (values set
in BLOCK_ERR) and notifies the content of
BLOCK_ERR.

Value of

BLOCK_ERR

Condition

MODE_BLK actual of PID block is LO.

IN.status of the PID block is either of the
following:

Bad-Device Failure

Bad-Sensor Failure

MODE_BLK.target of the PID block is O/S.

Local Override

Input Failure


Out of Service

TA0411.EPS

A4.18.2 Process Alarms

There are six types of process alarms. Only one
process alarm can be generated at the same time, and
the process alarm having the highest priority level from
among those occurring at the same time is generated.
The priority level is set for each process alarm type.

Parameter

Containing

Priority

Level Setting

Cause of Occurrence

Process

Alarm

Occurs when the PV increases
above the HI_HI_LIM value.

Occurs when the PV increases
above HI_LIM value.

Occurs when the PV decreases
below the LO_LIM value.

Occurs when the PV decreases
below the LO_LO_LIM value.

Occurs when the value of
[PV - SP] increases above the
DV_HI_LIM value.

Occurs when the value of
[PV - SP] decreases below the
DV_LO_LIM value.

HI_HI_PRI

HI_PRI

LO_PRI

LO_LO_LIM

DV_HI_PRI

DV_LO_PRI

HI_HI_ALM

HI_ALM

LO_ALM

LO_LO_ALM

DV_HI_ALM

DV_LO_ALM

TA0412.EPS

Advertising
This manual is related to the following products: