A5.3 transfer of las, A-25 – Yokogawa EJA115 User Manual

Page 63

Advertising
background image

IM 01C22T02-01E

A-25

APPENDIX 5. Link Master Functions

A5.3 Transfer of LAS

There are two procedures for an LM to become the LAS:

• If the LM whose value of [V(ST)

ϫV(TN)] is the smallest on a segment, with the exception of the current LAS,

judges that there is no LAS on the segment, in such a case as when the segment has started up or when the current
LAS has failed, the LM declares itself as the LAS, then becomes the LAS. (With this procedure, an LM backs up
the LAS as shown in the following figure.)

• The LM whose value of [V(ST)

ϫV(TN)] is the smallest on a segment, with the exception of the current LAS,

requests the LAS on the same segment to transfer the right of being the LAS, then becomes the LAS.

LM

Node address:

0x15

SlotTime = 5

LM

Node address:

0x16

SlotTime = 5

Node address: 0x14
SlotTime = 5

Basic device

Node address:

0xF1

Basic device

Node address:

0xF2

Basic device

Node address:

0xF3

Basic device

Node address:

0xF4

LAS

LAS

In the event that the current LAS in
this segment (node address 0x14)
fails, the LM with the address of 0x15
takes its place to become the LAS.

LM

FA0502.EPS

Figure 2. Backup of LAS

To set up an EJA as a device that is capable of backing
up the LAS, follow the procedure below.

NOTE: When changing the settings in an EJA, add the
EJA to the segment in which an LAS is running. After
making changes to the settings, do not turn off the
power to the EJA for at least 30 seconds.

(1) Set the node address of the EJA. In general, use

an address from 0x14 to [V(FUN) - 1].

Not used

LM device

Not used

Basic device

Default address

Portable-device address

V (FUN)

V (FUN) + V (NUN)

V (NUN)

0xFF

0xFC

0xFB

0xF8

0xF7

0x00

FA0503.EPS

0x0F

0x10

0x13

0x14

Bridge device

Figure 3. Node Address Ranges

(2) In the LAS settings of the EJA, set the values of

V(ST), V(MRD), and V(MID) to the same as the
respective lowest capability values in all the
devices within the segment. An example is shown
below.

Sub-

index

Element

EJA

Device

1

Device

2

Device

3

Description

1

3

6

SlotTime

MaxResponse
Delay

MinInterPdu
Delay

4

3

4

8

6

8

10

3

12

20

5

10

Capability value
for V(ST)

Capability value
for V(MRD)

Capability value
for V(MID)

TA0501.EPS

DlmeBasicInfo (EJA Index 361 (SM))

In this case, set SlotTime, MaxResponseTime, and
MinInterPduDelay as follows:

Subindex

Element

ConfiguredLinkSettingsRecord (EJA Index 369 (SM))

Description

Setting

(Default)

V (ST)

V (MRD)

V (MID)

20

6

12

(4095)

( 5)

( 12)

SlotTime

MaxResponseDelay

MinInterPduDelay

1

3

6

TA0502.EPS

(3) In the LAS settings of the EJA, set the values of

V(FUN) and V(NUN) so that they include the
node addresses of all nodes within the same
segment. (See also Figure 3.)

Subindex

Element

ConfiguredLinkSettingsRecord (EJA Index 369 (SM))

Description

Default Value

V (FUN)

V (NUN)

0x25

0xBA

FirstUnpolledNodeId

NumConsecUnpolledNodeId

4

7

TA0503.EPS

Advertising