1 interconnections – Yokogawa AXFA14G/C User Manual

Page 13

Advertising
background image

IM 1E6K2-E

4-19-5

4. OPERATION

4.8

When AM012 is used with AXFA14 or AXF integral
flowmeter

When using the AM012 calibrator with the AXFA14 or AXF integral flowmeter,

remove the amplifier only from the converter and put it in the dedicated junction box for
calibration. If /AXF is selected for the optional specifications, this junction box is
provided. The junction box can also be obtained separately. (Part No : F9559DJ)

4.8.1

Interconnections

POWER
90 to 132 VAC
(Power code: -1 and -2)
or
180 to 264 VAC
(Power code: -3)
50/60 Hz

AM012

G

EX1

EX2

N/-

Power supply

L/+

Junction Box Terminal

(G)

EX1

EX2

C

A

B

C

A

B

Connection of the AM012 signal and excitation cables

Connect the signal and excitation cables to the junction box.

Connect the power and ground cables to the AM012.

To next page

See Figure 4.8.1 for details of the connection.

See Figure 4.8.1 for details of the connection.

Change AM012 FUNCTIONS

Slide the AM012 FUNCTION switch to the ADMAG position

Figure 4.8.1

Interconnection Diagram

Connect the power cable to the AM012.
Ground the terminal of the AM012 to protect it from external noise.
After turning the power on, let the instrument warm up for at least ten minutes.

Advertising
This manual is related to the following products: