Yokogawa HART Communicator YHC5150X User Manual

Page 36

Advertising
background image

30

When connecting the communicator

to a loop with a resistive load greater than 250 Ωs, the HART

®

jacks

may be connected across the load, the loop + and -, or to the HART

®

device communication terminals. Refer

to the following diagram for connecting across the loop + and -.

.

Do not connect the communicator across the loop supply. This does not provide the
proper resistance and no HART

®

communication will be possible.

4.3 HART

®

Communication

Upon power up the communicator automatically polls for HART

®

devices in the range specified on the

HART

®

Setup System menu (default range is zero).


The HART

®

Connection status bar on the system screens indicates the current state of the HART

®

connection.


If you select the gray bar, no action will occur. The communicator will continue to send poll address
messages within the configured range as long as a device has not been selected for connection. If new
devices are added to the loop, within the configured range, they will be detected automatically.

Or the currently selected device is in the process of connecting.

When the bar is gray: there is no device connected;