5.2 ENTERING THE BATCH PARAMETERS

Step

Display

Description

Text

Ref

1

BATCH
OPTION
TEST
END
CAL

Enter Batch Parameters.
Option (if installed)
Check Input Signals.
Exit to normal operation.
Program Setup Parameters.

5.3
5.4

5.1

The following steps are displayed if BATCH is selected.

2

BATCH L

xxxxxx

Maximum Batch Size which can be
entered.
Set to 0 if no limit on batch size.

3.2

3

AUTO S
Off
On
xx:xx

Automatic restart feature.
Disable.
Enable.
If enabled, automatically restarts the
batch xx:xx (mins:sec) after the end of
the last batch.

3.2.4

4

START. T
xx:xx

Slow start time.
Time, in (minutes:seconds), when
Relay 2 will energise once the batch
has started.

3.2

5

PREST
xxxx

Prestop Quantity.
Quantity at which Relay 2 will
de-energise before the end of the batch.
(Eg. If the batch quantity is 100 litres
and Prest is 2 litres, relay 2 will
de-energise after 98 litres.)

3.2

34 Calibration