Input circuits, 1 the signal input – Yokogawa 414 Batch Controller User Manual

Page 41

Advertising
background image

6. INPUT CIRCUITS

6.1 THE SIGNAL INPUT

The basic circuit of the input is shown below. Both the current and voltage
signals are fed to a data selector but only one signal is processed, depending
upon whether a current (4-20mA or 0-20mA) or a voltage (1-5 V or 0-10 V)
input configuration is selected. The signal is fed to a voltage to frequency
convertor and transmitted to the microprocessor via an opto-coupler.

The microprocessor uses a crystal reference to provide an accurate measurement
of the incoming frequency. Once every 10 minutes a stable and accurate internal
reference is sampled and used to compensate the input. This technique ensures a
highly accurate measurement and makes periodic calibration unnecessary.

Input Circuits 39

Voltage to
Frequency

Microprocessor

Regulator

DC to DC
Convertor

Reference

10K

250
Ohm

Isolation

9

14

8

Voltage

Current