2. SPECIFICATION

General

Display:

6 digit LCD. 0.7" (17.8mm) high digits.

Display Update Rate:

0.25 seconds.

Transducer Supply:

8-24VDC field adjustable.
50mA maximum.

Power Requirements:

11.5 to 28.5 volts DC.
130 mA typical current (no options).
AC Mains: Set internally to 95-135 VAC or

190-260 VAC.

Operating Temperature:

0 to 55°C standard.

Dimensions:

5.7" (144mm) wide x 2.8" (72mm) high x
7.0" (178mm) deep.

Cutout:

5.5" (139mm) wide x 2.6" (67mm) high.

Analog Input

Input:

4-20mA, 0-20mA, 1-5 Volt or 0-10 Volt.
The input circuit is floating and isolated from
the power supply and outputs.

Span:

0.1000 to 50000.0000.

Zone:

0.0000 to 50000.0000.

Accuracy:

0.075% of full scale.

Self-Calibrating:

An internal reference is sampled every 10
minutes. Temp Co-efficient is 40ppm/C.
Aging is 20ppm/1000 hrs.

Integration:

The rate is integrated with a timebase
selectable to be in days, hours, minutes or
seconds.

Cut-off:

A cut-off point can be set below which the
rate is not integrated.

Specification 5