18

The Interface Solution Experts

Smart HART

Loop

Interface and Monitor

Custom Curve Parameters

The custom curve tab allows you to set up a custom
curve of up to 128 points. A custom curve can either
be created from scratch or loaded from a previously
created comma separated value (.csv) file. To
program the Analog Outputs parameters, change the
settings in the

Custom Curve tab, then press Download

Table. See the descriptions below of the various
sections of the screen.

Mode
Check the

Enabled box to begin programming the

custom curve.

Source Variable
The

Source Variable defines the variable that the

custom curve will calculate. Notice that if you select a
scaled variable, you may need to click on the

Scaling

tab and verify the settings for your scaled variable.

Quick Set
The

Quick Set button causes the software to configure

the HIM’s custom curve settings to match those
currently entered in the PC Software.

Figure 14. Custom Curve Tab

Custom Curve Variable
The

Custom Curve Variable displays up-to-the-second

information on the value of the Custom Curve. Press
the

Monitor button to display the variable information.

Custom Curve
The middle section of the screen displays the custom
curve table. After enabling custom curve mode and
setting the variable to be monitored, continue by
selecting the number of points for the curve. Enter the
actual linearization points into the custom curve table,
inserting the source variable into the X Column, and
the corresponding data (i.e. the °C, °F, Gallons, PSIG,
Millimeters, etc.) into the Y Column.

Note:

When entering data in the linearization table, make

sure that you enter a number into every open cell.

Custom Curve File
These buttons allow you to manipulate custom curve
files, including the important

Save Table command that

will save a table to your hard drive.

Upload Table
Moves a custom curve file from the connected HIM to
the PC Software for editing or storage.

Download Table
Configures the HIM by downloading the custom curve
table from the PC Software to the HIM.

Save Table
Saves a displayed custom curve table to memory on
your computer’s hard drive.

Load Table
Loads a previously saved custom curve table.

Clear Table
Clears the displayed custom curve table.

When you have finished changing all your settings,
download the information to the HIM using the
Download Table button. If you have selected a scaled
variable, you should also click on the

Scaling tab and

set the scaling parameters.