Bench checking the him, Smart hart, Loop interface and monitor – Yokogawa HIMHART User Manual

Page 9

Advertising
background image

The Interface Solution Experts

9

HIM

Smart HART

Loop

Interface and Monitor

Figure 5. Bench Checking the HIM Using the Transmitter
Excitation (+TX) Terminal to Power a Transmitter

Figure 6. Bench Checking the HIM Without Using the
Transmitter Excitation (+TX) Terminal to Power a Transmitter

Bench Checking the HIM

If you would like to configure the HIM before
attaching it to the loop, you need to hook it up
with the equipment listed in Table 1. Refer to
Figures 5 and 6 for instructions on how to bench
check the HIM either with or without taking
advantage of the Transmitter Excitation (+TX)
terminal. If you need further descriptions of the
terminals, see Table 2.

READY

INPUT

TRIP 2

TRIP 1

COM

0

ADDR

For a HART Transmitter, the
resistor must be >250

and <1100 ohms.

For a HART Receiver, such as a
valve positioner, no resistor is necessary.

HART

Field Device

or

Simulator

Sensor

Input

Optional

Optional

Checks for

continuity

24Vdc
Power

R

+IN

NO

NC

DC

GND

COM

–IN

+

+

+

+

Multimeter

Multimeter

24Vdc
Power

DCC

READY

INPUT

TRIP 2

TRIP 1

COM

0

ADDR

Optional

Checks for

continuity

NO

NC

DC

GND

COM

+

+

Multimeter

Multimeter

24Vdc
Power

DCC

HART

Field Device

or

Simulator

Sensor

Input

Equipment Hook-Up

for HART field device using

Transmitter Excitation

R

+TX

–IN

+IN

+

R must be > 250 and <1100 Ohms