Sub-component documentation, 1 compressed air line sizes – Yokogawa Advanced Reflux Sampler User Manual

Page 13

Advertising
background image

13

All Rights Reserved. Copyright © 2011, Yokogawa Electric Corporation. Subject to change without notice.

April 2011

IM 11A00V01-01E-A

10. SUB-COMPONENT DOCUMENTATION

This section contains sub-component manufacturers information and supporting documentation that may be of use to

operators.

10.1 Compressed Air Line Sizes

Compressed air lines should be sized to hold pressure drops to a minimum. So not used restrictive fittings such as quick

connects. They can “starve” the Vortex Tube by causing line pressure drop. The following chart gives suggested line sizes

for pipe and hose.

Line Sizes for Runs Up To:

10 FT

(3 M)

10 - 50 FT

(3 - 15 M)

50 - 100 FT

(

15 - 30.5M)

Pipe

Hose

Pipe

Hose

Pipe

Hose

1/4”

3/8”

3/8”

1/2”

1/2”

5/8”

10.1.1 Compressed Air Supply

For best performance, use line pressure 80 to 100 PSIG (5.5 – 6.9 BAR). Vortex Tubes are rated in SCFM (SLPM) at 100

PSIG (6.9 BAR) supply pressure.
With proper filtration and separation for dirt, moisture and oil from the compressed air supply, the Vortex Tube will run for

years with no maintenance required. Use a 25 micron or smaller filter separator that is sized to SCFM (SLPM) rating of the

Vortex Tube.
To prevent problems associated with oil, use an appropriate Oil Removal Filter for Vortex Tubes up to 30 SCFM (850

SLPM) . The oil removal filter should be used downstream from the automatic drain filter separator. Filter should be used

within 10 to 15 ft ( 3 to 4.6 m ) of each Vortex Tube.

For Replacement or Repair filter and regulator parts contact Yokogawa.

10.1.2 Setting the Vortex Tube

Hot and cold temperatures produced by a Vortex Tube are infinitely variable by adjusting the slotted valve at the hot air

exhaust. Opening the valve reduces the cold airflow and the cold air temperature, Closing the valve increases the cold

airflow and the cold air temperature.
Set the Vortex Tube with a thermometer. To measure temperature accurately, it should be inserted into the cold muffler or

a piece of tubing on the cold end exhaust.

10.1.3 Troubleshooting & Maintenance

If the Vortex Tubes Does Not perform properly, check for these common problems:

1.) Loosed Cold Cap or Cold Muffler- A loosed cold cap or cold muffler will cause poor performance. Make sure it is tight.
2.) Inlet Pressure- Low inlet pressure supply will cause poor performance. Measure the pressure at the compress air

Advertising