Measuring, Parameterization, 1 main menu – Yokogawa Pneumatic Retractables RF20H User Manual

Page 12: 2 automatic mode

Advertising
background image

IM 12B06K07-E-E

6. Parameterization

There is the risk of damaging the system or
that process fluid or cleaning solution issues
in an uncontrolled manner!

• Wear suitable protective clothing
• Have the system only parameterized by instructed

skilled personnel!

• Inspect all sealings and all connections of the

fitting prior to running the process

Wear protective glasses and protective
clothing when you start the system!

The control is generally operated as follows:

Main Menu

Automatic Mode

Manual Mode
Parameter
System

UP

DOWN

• The upper line shows the current menu.
• The lower line shows the functions of the soft keys.
• The function which can be selected is shown

invertedly in the respective case and selected by
means of the Enter button.

• The ESC button brings you back one menu each

time.

6.1 Main Menu

In the Main Menu, you can choose between the
individual processes.

Main Menu

Automatic Mode

Manual Mode
Parameter
System

UP

DOWN

• When you select the Automatic Mode, the

parameterized automatic process in the control
starts (see chapter 6.2).

• When you select the Manual Mode, you reach the

level for manual operation (see chapter 6.3).

• When you select Parameters, you reach the

parameterization (see chapter 6.4).

• When you select System, you reach the system

control (see chapter 6.5).

6.2 Automatic Mode

The parameterized process runs in automatic mode
and the display shows the following:

Automatic

12:22:17

* Measuring *

In 45 Min. Service

Info

Para

Stop

• The first line shows Automatic and the current

time in HH:MM:SS.

• The middle shows the current function in big

letters.

• Below, the time remaining until the next function

or action starts is shown.

• The soft keys are assigned to the following

parameters:
Info

Para

Stop

Info Shows information relating to the control

via preset times, the total time of a cleaning
cycle and the state of the software.

Para Leads you to the parameterization of the

cleaning and interval times (chapter 6.4).

Stop Automatic can be interrupted here.


By pressing the stop button, you can select
between an Emergency Stop and a “gentle”
Stop.

In case of an Emergency Stop, the fitting
immediately moves to the service position,
stays there and is not rinsed.

In case of stop, the fitting moves to
the service position and finishes with a
parameterized rinsing process.

CAUTION!

DANGER!

WARNING!

CAUTION!

DANGER!

WARNING!

Advertising