Yokogawa Button Operated DX2000 User Manual

Page 7

Advertising
background image

6

2.3. Alarm

Alarm types in LOG input mode

¾

H, L, T, and t only.

Set the alarm value using a voltage.
Computing method of alarm values

¾

Computing equation of the digital display value

From Y = 10

(SU-SL)*(X-VL)/(VU-VL)+SL

logY = (SU-SL)*(X-VL)/(VU-VL)+SL
X = (logY-SL)*(VU-VL)/(SU-SL)+VL

¾

For a computation example, see Table 2-2.

Alarm hysteresis fixed to 0%.

¾

The alarm hysteresis settings specified in the basic setting mode for the

measurement channel are invalid.

Table 2-2 Computation Example of Alarm Values

Alarm Value

Span

Lower

Span

Upper

Lower Limit

of Exponent

Upper Limit of

Exponent

Equivalent

Display

Voltage

Equivalent

1 5 2

8 5.0E+6 4.133

1 5 2

8 1.0E+6 3.667