Pa program pattern end signal – Yokogawa Data Acquisition with PID Control CX2000 User Manual

Page 13

Advertising
background image

13

IM 04L31A01-05E

PA

Program pattern end signal

When the event output setting method is separate

Syntax

PA p1,p2,p3

<terminator>

p1:

Pattern number (1 to 30)

p2:

Enable/disable relay output (Off, On)

p3:

Relay number*

*: DO001 to DO006

DO101 to DO106

DO201 to DO206

RO001 to RO012 (expansion module)

SW001 to SW036 (internal switch)

DO001 to DO006, SW001 to SW018 on the CX1000.

Query

PA?

When the event output setting method is Common

Syntax

PA p1,p2

<terminator>

p1:

Enable/disable relay output (Off, On)

p2:

Relay number*

*: DO001 to DO006

DO101 to DO106

DO201 to DO206

RO001 to RO012 (expansion module)

SW001 to SW036 (internal switch)

DO001 to DO006, SW001 to SW018 on the CX1000.

Query

PA?

Basic Setting Commands (Measurement)

XU

Sets the channel identification display, memory alarm
time, language, whether or not to use the partial expanded
display function and the batch function

Syntax

XU p1,p2,p3,p4

<terminator>

p1:

The display used to identify the measurement/computation channels (TAG,

CHANNEL)

p2:

Memory alarm time (OFF, 1H, 2H, 5H, 10H, 20H, 50H, 100H)

p3:

Language (ENGLISH, JAPANESE, GERMAN, FRENCH, CHINESE)

p4:

Use/Not use partial expanded display function (USE, NOT)

Query

XU?

Example

Set the display used to identify the measurement/computation channels to channel

numbers, the memory alarm length to 1 hour, the language to English, use the partial

expansion function and the batch function.

XU CHANNEL,1H,ENGLISH,USE,USE

Description

The SP command can be used when parameter p4 of this command is set to USE.

Communication Commands