With the functional changes, the operations on the CX1000/CX2000 change as follows:

Event Output Setting in Basic Control Settings (New Operation)

Select Common or Separate by carrying out the procedure described below.

Common (factory default setting)

Set a common event output setting for all program patterns.

Separate

Set the event output for each program pattern.

Displaying the Setting Display

On the CX2000

Press the keys in the following sequence:

MENU key

(switch to the setting mode (control)) >

Hold down the FUNC key for 3

seconds

(switch to the basic setting mode) > #10 soft key (select [Control]) >

#2

soft key

(select [DI/DO/SW-registration, AUX (Alarm mode...)])

From the operation display, use the above keys to open the following setting display.

On the CX1000

Press the keys in the following sequence:

MENU key

(switch to the setting mode (control)) >

Hold down the FUNC key for 3

seconds

(switch to the basic setting mode) >

#12 soft key

(select [Control]) >

#4

soft key

(select [AUX (Alarm mode...)])

From the operation display, use the above keys to open the following setting display.