Yokogawa Standalone MW100 User Manual

Page 20

Advertising
background image

20

IM CA150E

A defi nition screen should now appear for the ETHERNET-MODULE. In the Name fi eld – type MW100 (or the desired connection
name). Comm Format can be left at Data – DINT and IP Address should be set to the IP address of the MW100. Connection
Parameters
are where the inputs and outputs are defi ned. In the Assembly Instance table below there are Instance IDs that
correspond to channels within the MW100. All Instance IDs of Kind Producer can be assigned to Input (e.g., Instance ID 130
would point the Input at Communication Channel C001). All Instance IDs of Kind Consumer can be assigned to Output (e.g.,
Instance ID 131 would point the Output at Communication Channel C101). Size refers to how many channels are available per
Instance ID. In the Assembly Instance table, all Instance IDs can have Size 100 except for MW100 Channels 001-060 that have
a maximum size of 60. A smaller Size can be used if fewer channels are needed (e.g., below only 10 channels per Instance ID
are confi gured). Confi guration can be set to Instance 190 with Size 0. In the case that no Outputs are used, Output Instance
can be set to 191, Size 0 for heartbeat purposes (allows MW100 to stop broadcasting for data if heartbeat goes away).

Confi guring an MW100 as a Generic Ethernet Module

Now that the MW100 is added, it should appear in RSLogix 5000

®

as a connection in the Controller Organizer.