Attachment Positions and Channel Numbers

The figure below shows how the channel numbers are identified on the PC.

MX100

0

1

2

3

4

5

Slot number

001 to 010

011 to 020

021 to 030

031 to 040

041 to 050

051 to 060

Channel number in the unit

*2

Representation of channel numbers:

Channel numbers in a unit (001 to 060)

Unit number (00 to 89)

*1

*2 The last one digit on a 4-channel module is 1 to 4,

the last one digit on a 6-channel module is 1 to 6,

the last one digit on a 8-channel module is 1 to 8.

*1 Fixed to 00 when connecting using

the MX100 Standard software;

set between 00 and 19 when using

MXLOGGER software; and set

between 00 and 89 when using

the MW100 Viewer software.

General Precautions When Wiring the Input/Output Signal Wires

WARNING

• To prevent the possibility of electric shock when wiring, confirm that the

power supply source and the signal source are turned OFF. After making the
connections, secure the terminal cover and do not touch the terminals with your
hands.

• For signal wires on which voltage exceeding 30 VAC/60 VDC is applied relative

to the ground potential or between signals, use double (reinforced) insulation
wires. For all other signal wires, use basic insulation wires. For the withstand
voltage of insulation wires, see the table below.

Applied Voltage (Vrms or VDC) Basic Insulation Double (reinforced) Insulation

0 to 150

1350 Vrms

2700 Vrms

151 to 300

1500 Vrms

3000 Vrms

301 to 600

2210 Vrms

3700 Vrms

• To avoid electric shock when removing the screw terminal block and screw

terminal plate, be sure to attach the screw terminal block and screw terminal
plate to the input modules before inputting signals. Electric shock or fire can
result if signals are applied to the terminals when the screw terminal block or
screw terminal plate is removed from the input modules.

• When wiring to screw terminals, use round, insulation coated crimp-on lugs on

the terminals (4-mm screws on the screw terminal block, and 3-mm screws on
the screw terminals and screw terminal plate) that do not come out when loose.

• To prevent fire, use signal wires of the following temperature ratings.

Module Type

Temp. Rating

Screw terminal block

75°C

Universal input module, DCV/TC/DI input module, 4-wire RTD

resistance input module, Strain input module, Pulse input module,

Digital input module, Digital output module

80°C

Analog output module, PWM output module

85°C