2.4

Readng Data from a Modbus Devce and
Transferrng the Data as the Montor Server

When you run the executable function, data is read in from the Modbus devices, the PC

becomes the monitor server, and data is transferred to DAQLOGGER or Remote Monitor.

The executable function can be run as a process or a service. When run as a process,

the executable function closes when logging off Windows. When run as a service, the

executable function is registered in Windows as an automatically executable service.

When run as a service, the executable function continues processing even when the

user has logged off of Windows. Also, the executable function is run automatically as

soon as the PC is turned ON (prior to log in). However, the software can only be run as a

service by a user with Administrator privileges. Services cannot be executed when using

Windows Vista.

Note

The maximum number of DAQLOGGERs or Remote Monitors that can be connected at once is

16.

Runnng the Executable Functon

Procedure

1.

Enter environment settings. (See section 2.2, “Entering Environment Settings.”)

Runnng from the Menu Bar

2.

To run the function as a process, click the Process Execution button or choose

Execute > Process from the menu bar.

Process execution button

Service execution button

To run the function as a service, click the Service execution button or choose

Execute > Servce from the menu bar.

The Practice Status item in the Practice/Status tab displays “Process” or “Service,”

as well as the name of the connected client, connection status, and the addresses

of any disconnected DAQLOGGERS and Remote Monitors.