3-4

IM WX1-05E

Logcal Confguraton

Item

Descrpton

Lmt

Tag

Indicates one data item.

300

Group

Assigns tags. Up to 32 tags can be assigned to a group.

50

Logcal Confguraton Dagram

TAG001

GateMODBUS

TAG002
TAG003
TAG004

TAG200

Tag

Assignments

Group

Group

Acquston Condtons

The following items are included in the acquisition conditions.

• Data scan interval (0.5–3600 sec)

For information on the data acquisition operation, see page 3-6, “Acquiring Data at

Fixed Intervals.”

• Timeout time (1–10 sec)

• Retry Use (ON/OFF).

• Retry Interval (30–3600 sec.)

Tag

A tag is a name for a data value. You can use up to 100 tags with GateMODBUS. Data

obtained from the Modbus registers is assigned to each tag. The following items are

included in tag settings.

• Used serial ports (COM1–COM9) and Ethernet ports (Ether1 to Ether16)

• The read Modbus function (03 or 04)

• Register numbers read

For Modbus function 03: 40001–49999, 400001–465535

For Modbus function 04: 30001–39999, 300001–365535

• Data Type

See page 3-8, “Data Type.”

• Scaling variable

See page 3-10, “Data Scaling.”

• Decimal place

• Upper/lower span value

• Tag name

• Unit

3.2 Detaled Descrpton of Functons