4. DESCRIPTION OF FRONT PANEL

4.1 Front Panel

The communications connector in the front panel is used for

setting up parameters through a PC (VJ77 PC-based Parameters

Setting Tool) or the Handy Terminal.

Communications connector

Alarm-1 LED

Alarm-2 LED

4.2 Connector for Communication

Use the connector for communication when setting the

parameters using a PC (VJ77 Parameters Setting Tool) or the

Handy Terminal

How to connect with the setting tool

Modular jack conversion

adapter (E9786WH)

[Provided with VJ77]

JHT200

Handy Terminal

JUXTA communication cable

with 5-pin connector (F9182EE)

[Provided with VJ77 and JHT200]

Dedicated adapter (E9789HA)

[Provided with VJ77]

PC which is installed

with the VJ77

Dedicated cable (E9786WK)

[Provided with VJ77]

• Use the VJ77 of version R1.04 or later.

• The modular jack conversion adapter does not come with the

JHT200 Handy Terminal. It is sold separately.

5. SETTING PARAMETERS

Set the parameters using a PC (VJ77 Parameter Setting Tool) or

the Handy Terminal. Refer to

“8. LIST OF PARAMETERS” in this

manual and the User’s Manual for VJ77 PC-based Parameters

Setting Tool (IM 77J01J77-01E) or the User’s Manual for JHT200

Handy Terminal (IM JF81-02E). Parameters are indicated inside

the

[ ].

5.1 Settings Related to Inputs and Outputs

5.1.1 Input Range Unit

When referring and setting the input range, select and set “Hz”

or “kHz” in

[D10: UNIT]. Select “kHz” when input range is over

32000Hz.

5.1.2 Conversion Mode

Select and set the action of the instrument from “F/V

CONVERTER” (F/V conversion) or “INTEGRATOR” (pulse

integrator) in

[D19: SELECT MODE].

F/V converter: Set when converting 0 to 100% of frequency

input to 0 to 100% of analog output, and

outputting it.

INTEGRATOR: Set when converting 0 to 100% of frequency

in put to 0 to 100% of analog output after

computing the average frequency from the

pulse number integrated per sample time, and

outputting it.

5.1.3 Sample Mode

Select and set “AUTO” or “MANUAL” in

[D20: SAMPLE

MODE], when the conversion mode is set to “INTEGRATOR.”
AUTO:

Outputs the sample time forcibly on the provided

MANUAL: Sets the sample time within setting range.

5.1.4 Sample Time

When the sample mode is set to “MANUAL”, set the sample

time in numerical value in

[D21: SAMPLE TIME], Sample

time setting range: 0.1 to 100 seconds, by 0.1 second When

the sample mode is set to “AUTO”, the sample time is forcibly

decided on the following conditions.

0.1 second when F

100

(100% input frequency) is 1kHz or more

(1/F

100

) 100 seconds when F

100

is over 1Hz and below 1kHz

100 seconds when F

100

is 1Hz or less.

5.1.5 Input Range

Set the 0% value of input range in

[D22: INPUT1L_RNG],

and 100% of input range in

[D23: INPUT1H_RNG] within the

numerically specified range.

Note

In case the input range is changed after factory-ship,

the instrument may not work within the rated accuracy

range depending on the changed input range. Perform

the adjustment following the maintenance of this

instruction manual after changing the input range.

5.1.6 Input Filter

When the chattering noise is generated in input, the input filter

is used to restrain the influence. Select and set “ON” in

[D50:

INPUT FILTER], then the input filter for time constant of about

10ms will be connected.

5.1.7 Direction of Output Action

Analog output signals can be reversed. To reverse the

signal from output-1, set

[D38: OUT1 DR] to REVERSE. For

output-2, set

[D39 OUT2 DR] to REVERSE. To return the

output-1 signal to normal, set D38: OUT1 DR to DIRECT. For

output-2, set D39: OUT2 DR to DIRECT.