List of parameters, Maintenance, 1 calibration apparatus – Yokogawa JUXTA VJQ8 User Manual

Page 5: 2 calibration procedure

Advertising
background image

5

IM 77J01Q08-01E 4th Edition

Mar. 02, 2012-00

8. LIST OF PARAMETERS

Parameter Display

Item

MODEL

Model

TAG NO

Tag no.

SELF CHK

Self-check result

A

DISPLAY1

Display1

A01 INPUT1

Input value 1

*1

A05 OUTPUT1

Output value 1

A06 OUTPUT2

Output value 2

A07 ALM1 STATUS

Alarm-1 status

A08 ALM2 STATUS

Alarm-2 status

A31 COUNTER1

Integrating counter 1

A32 COUNTER2

Integrating counter 2

A33 COUNTER3

Integrating counter 3

A34 COUNTER4

Integrating counter 4

A54 STATUS

Status

(*2)

A56 REV NO

Rev. no.

A58 MENU REV

MENU REV

A60 SELF CHK

Self-check result

B

DISPLAY2

Display2

B01 INPUT1

Input value 1

*1

B05 OUTPUT1

Output value 1

B06 OUTPUT2

Output value 2

B07 ALM1 STATUS

Alarm-1 status

B08 ALM2 STATUS

Alarm-2 status

B31 COUNTER1

Integrating counter 1

B32 COUNTER2

Integrating counter 2

B33 COUNTER3

Integrating counter 3

B34 COUNTER4

Integrating counter 4

B60 SELF CHK

Self-check result

D

SET (I/O)

Setting (I/O)

*3

D01 TAG NO.1

Tag no. 1

D02 TAG NO.2

Tag no. 2

D03 COMMENT1

Comment 1

D04 COMMENT2

Comment 2

D10 UNIT

Range unit

D13 LOW CUT

Low input cut point

D19 SELECT MODE

Conversion mode

D20 SAMPLE MODE

Sample mode

D21 SAMPLE TIME

Sample time

D22 INPUT1 L_RNG

Input low range

D23 INPUT1 H_RNG

Input high range

D38 OUT1 DR

Direction of output-1 action

D39 OUT2 DR

Direction of output-1 action

D50 INPUT FILTER

Input filter

D60 SELF CHK

Self-check result

E

SET(ALM)

Setting (alarm output)

*3

E03 SET POINT1

Alarm-1 setting

E04 SET POINT2

Alarm-2 setting

E05 ALM1 ACTION

Direction of alarm-1 action

E06 ALM2 ACTION

Direction of alarm-2 action

E09 HYSTERESIS1

Alarm-1 hysteresis

E10 HYSTERESIS2

Alarm-2 hysteresis

E11 ON DELAY1

Alarm-1 ON delay setting

E12 ON DELAY2

Alarm-2 ON delay setting

E13 OFF DELAY1

Alarm-1 OFF delay setting

E14 OFF DELAY2

Alarm-2 OFF delay setting

E15 RL1 ACTION

Direction of alarm-1 relay

action

E16 RL2 ACTION

Direction of alarm-1 relay

action

E60 SELF CHK

Self-check result

F

SET(COM)

Setting (communication)

*3

F01 PROTOCOL

Communication protocol

F02 ADDRESS

Address

F03 BAUD RATE

Baud rate

F04 PARITY

Parity

F05 DATA LEN

Data Length

F06 STOP BIT

Stop bit

F07 INPUT DEC PT

Decimal point position of

input

F60 SELF CHK

Self-check result

P

ADJUST

Adjustment

P12 OUT1 0%

0% adjustment of output-1

P13 OUT1 100%

100% adjustment of output-1

P14 OUT2 0%

0% adjustment of output-2

P15 OUT2 100%

100% adjustment of output-2

P60 SELF CHK

Self-check result

Q

TEST

Test

Q02 OUT1 TEST

Forced output-1

Q03 OUT2 TEST

Forced output-2

Q04 ALM1 TEST

Forced output (alarm)

Q05 ALM2 TEST

Forced output (alarm)

Q60 SELF CHK

Self-check result

*1 Instantaneous frequency is displayed even if conversion

mode is pulse integration.

*2 The Status is displayed for service personnel to see

history records.

*3 There are items not displayed depending on what output-2

is specified.

9. MAINTENANCE

The product starts running immediately when the power is turned

on; however, it needs 10 to 15 minutes of warm-up before it

meets the specified performance.

9.1 Calibration Apparatus

• A calibrator (Yokogawa 7561 or equivalent)

• A precision resistor of 250 Ω ±0.01%, 1W

Setting tool for adjustment (Refer to

“4.2 Connector for

Communication” in this manual.)

9.2 Calibration Procedure

1. Connect the instruments as shown below. First adjust the

output-1 signal and then the output-2 signal.

10

11

3 2 1

4

5

6

7

8

9

Power supply

11

10

8

L

+

N

GND

3

4

+

Input

Calibrator

Calibrator

2

5

Output-2

R

+

Calibrator

2

5

Alarm-1

ALM1

COM

+

Calibrator

6

5

Alarm-2

ALM2

COM

+

Calibrator

7

9

Output-1

R

+

R: For current output using 250 Ω

precision resistor

2. Use the calibrator and apply input signals equivalent to 0, 25,

50, 75, and 100% of the input span to the product.

3. Check to see the corresponding output voltages are 0, 25, 50,

75, and 100% respectively and within the specified accuracy

rating. (“R” is used for current output.)

For alarm output, check the relay action by the alarm indicator

lamp or resistance of output terminals.

• Use the setting tool (VJ77 Parameter Setting Tool or JHT200

Handy Terminal) to adjust the input/output signals.

User’s Manual for VJ77 [Document No.: IM 77J01J77-01E];

however, use the VJ77 of version R1.04 or later.

User’s Manual for JHT200 [Document No.: IM JF81-02E]