4. DESCRIPTION OF FRONT PANEL

4.1 Front Panel

The communications connector in the front panel is used for

setting up parameters through a PC (VJ77 PC-based Parameters

Setting Tool) or the Handy Terminal. The alarm-1 and alarm-2

LEDs light up if an alarm occurs (those LEDs are provided only

when the output-2 is specified for alarm output).

Communications connector

Alarm-1 LED

Alarm-2 LED

4.2 Connector for Communication

Use the connector for communication when setting the

parameters using a PC (VJ77 Parameters Setting Tool) or the

Handy Terminal

How to connect with the setting tool

Modular jack conversion

adapter (E9786WH)

[Provided with VJ77]

JHT200

Handy Terminal

JUXTA communication cable

with 5-pin connector (F9182EE)

[Provided with VJ77 and JHT200]

Dedicated adapter (E9789HA)

[Provided with VJ77]

PC which is installed

with the VJ77

Dedicated cable (E9786WK)

[Provided with VJ77]

● Use the VJ77 of version R1.04 or later.

● The modular jack conversion adapter does not come with the

JHT200 Handy Terminal. It is sold separately.

5. SETTING PARAMETERS

Set the parameters using a PC (VJ77 Parameter Setting Tool) or

the Handy Terminal. Refer to

“7. LIST OF PARAMETERS” in this

manual and the User’s Manual for VJ77 PC-based Parameters

Setting Tool (IM 77J01J77-01E) or the User’s Manual for JHT200

Handy Terminal (IM JF81-02E). Parameters are indicated inside

the

[ ].

5.1 Settings Related to Inputs and Outputs

5.1.1 Total resistance

Set the total resistance in

[D06: RESIST].

Setting range: 100 to 10000 Ω

5.1.2 Input Range

Set the 0% value of input range in

[D22: INPUT1 L_RNG],

and the 100% value of input range in

[D23: INPUT1 H_RNG].

5.1.3 Burnout

Set the burnout operation in

[D30: BURN OUT].

Set “OFF”, “UP”, or “DOWN.”

5.1.4 Direction of Output Action

Analog output signals can be reversed. To reverse the

signal from output-1, set

[D38: OUT1 DR] to REVERSE. For

output-2, set

[D39 OUT2 DR] to REVERSE. To return the

output-1 signal to normal, set

[D38: OUT1 DR] to DIRECT.

For output-2, set

[D39: OUT2 DR] to DIRECT.

5.2 Settings Related to Communication

Function

Set the following parameters when output-2 is specified

for communication function. For more information on the

communication function, see the Instruction Manual for VJ Series

Communication Function (IM 77J1J11-01E).

5.2.1 Communication Protocol

Set the communication protocol by selecting from among

PCLINK, PC-LINK WITH SUM, MODBUS ASCII, MODBUS

RTU, and LADDER in

[F01: PROTOCOL].

5.2.2 Communication Address

Set the address number of the isolator numerically in a range

of 1 to 99 in

[F02: ADDRESS].

5.2.3 Baud Rate

Set the baud rate by selecting from among 1200, 2400, 4800,

and 9600 bps in

[F03: BAUD RATE].

5.2.4 Parity

Select and set NONE, EVEN, or ODD in

[F04: PARITY].

5.2.5 Data Length

Select and set 7 bits or 8 bits in

[F05: DATA LEN].

5.2.6 Stop Bit

Select and set 1 bit or 2 bits in

[F06: STOP BIT].

5.2.7 Input Decimal Point Position

Number of digits of decimal places can be set.

Select and set among 0 to 5 digits in

[F07: INPUT DEC PT].

5.3 Settings Related to Alarm Output

Set the following parameters when output-2 is specified for alarm

output.

5.3.1 Alarm Setpoints

Set the alarm setpoints of alarm-1 and alarm-2 in

[E03: SET

POINT1] and [E04: SET POINT2] numerically.

• Setting range: A range of 0 to 100% of input range

• Setting resolution: 0.1%

5.3.2 Direction of Alarm Action

Select the direction of alarm-1 action and that of alarm-2

action from among HIGH ALM (high-limit alarm) and LOW

ALM (low-limit alarm) and set each in

[E05: ALM1 ACTION]

(direction of alarm-1 action) or

[E06: ALM2 ACTION]

(direction of alarm-2 action).

• To activate alarm status when input signal ≥ alarm setpoint,

select HIGH ALM.

• To activate alarm status when input signal ≤ alarm setpoint,

select LOW ALM.

5.3.3 Hysteresis

Set alarm-1 and alarm-2 hysteresis, in

[E09: HYSTERESIS1]

and

[E10: HYSTERESIS2]. Hysteresis is a value added to the

alarm setpoint in order for an alarm status to be released (to

normal) after the alarm status has been activated. The alarm

status will be released in the following conditions, depending

on the direction of alarm action.

1. *

When HIGH ALM (high-limit alarm) is set: Alarm is

released when input signal < (alarm setpoint - hysteresis).

2. *

When LOW ALM (low-limit alarm) is set: Alarm is

released when input signal > (alarm setpoint + hysteresis).

• Setting range: A range of 0 to 100% of input range

• Setting resolution: 0.1%