5.3.4 Alarm ON Delay and Alarm OFF Delay

Set alarm-1 and alarm-2 ON delays in

[E11: ON DELAY1] and

[E12: ON DELAY2] and then alarm-1 and alarm-2 OFF delays

in

[E13: OFF DELAY1] and [E14: OFF DELAY2]. An alarm

ON delay is a delay time from the establishment of alarm

condition to alarm output; an alarm OFF delay is a delay time

from the establishment of return-to-normal condition to output.

• Setting range: 0 to 999 seconds

• Setting resolution: 1 second (Note that about 0.2 second will

be added to set time to prevent erroneous operation.)

For example, when an alarm ON delay is set to 1 second,

alarm output is generated if alarm status continues for

more than 1 second after the input value exceeds the

alarm setpoint. Further, when an alarm OFF delay is set

to 2 seconds, alarm output is released if normal condition

continues for more than 2 seconds after the input value has

returned to normal from the alarm status.

5.3.5 Direction of Relay Action

Set the direction of relay energizing in alarm-1 normal

condition and alarm-2 normal condition by selecting from

among NRM DEENERGIZED (de-energized under normal

condition) and NRM ENERGIZED (energized under normal

condition) in

[E15: RL1 ACTION] and [E16: RL2 ACTION]

and set them.

6. DESCRIPTION OF ALARM ACTIONS

This chapter describes examples of alarm actions under the

following conditions.

Item

Alarm-1

Alarm-2

Parameter

Setpoint Parameter

Setpoint

Direction of alarm

action

E05: ALM1 ACTION High-limit

alarm

E06: ALM2 ACTION Low-limit

alarm

Alarm setting

E03: SET POINT1

80%

E04 : SET POINT2

15%

Hysteresis

E09: HYSTERESIS1 10%

E10 : HYSTERESIS2 5%

Alarm ON delay

E11: ON DELAY1

1 sec.

E12 : ON DELAY2

3 sec.

Alarm OFF delay

E13: OFF DELAY1

2 sec.

E14 : OFF DELAY2 4 sec.

Description of alarm

actions

The alarm sounds if the

condition where the input value

is 80% or more of high-limit

alarm continues for more than 1

second. After the alarm sounds,

when the condition where

input value is less than 70%of

the high-limit alarm continues

for more than 2 seconds, the

status returns to normal

The alarm sounds if the

condition where the input value

is 15% or less of low-limit

alarm continues for more than

3 seconds. After the alarm

sounds, when the condition

where input value is more than

20% of the low-limit alarm

continues for more than 4

seconds, the status returns to

normal.

Alarm-1 action

Alarm-2 action

Normal

Normal

Normal

Normal

Alarm

Alarm

[%]

0

20

15

40

60

80

100

1 sec.

2 sec.

3 sec.

4 sec.

Alarm-2 hysteresis (5%)

Alarm-1 hysteresis (10%)

Alarm-1 setpoint (80%)

Alarm-2 setpoint (15%)

Elapsed time 1 sec.

[1]

[2]

[3]

[4]

[1]: Alarm status does not continue for more than 1 second after

the alarm conditions are established at alarm-1.

[2]: Normal status does not continue for more than 2 seconds after

the normal conditions are established at alarm-1.

[3]: Alarm status does not continue for more than 3 seconds after

the alarm conditions are established at alarm-2.

[4]: Normal status does not continue for more than 4 seconds after

the normal conditions are established at alarm-2.

Alarm-1

ON delay

Alarm-2

ON delay

Alarm-2

OFF delay

Alarm-1

OFF delay

Alarm conditions

established

Alarm conditions

established

Normal conditions

established

Normal conditions established

High-limit alarm ON

Low-limit alarm ON

High-limit alarm OFF

Low-limit alarm OFF

7. LIST OF PARAMETERS

Parameter Display

Item

MODEL

Model

TAG NO

Tag no.

SELF CHK

Self-check result

A

DISPLAY1

Display1

A01

INPUT1

Input value 1

A05

OUTPUT1

Output value 1

A06

OUTPUT2

Output value 2

A07

ALM1 STATUS

Alarm-1 status

A08

ALM2 STATUS

Alarm-2 status

A54

STATUS

Status

*1

A56

REV NO

Rev. no.

A58

MENU REV

MENU REV

A60

SELF CHK

Self-check result

B

DISPLAY2

Display2

B01

INPUT1

Input value 1

B05

OUTPUT1

Output value 1

B06

OUTPUT2

Output value 2

B07

ALM1 STATUS

Alarm-1 status

B08

ALM2 STATUS

Alarm-2 status

B60

SELF CHK

Self-check result

D

SET (I/O)

Setting (I/O)

*2

D01

TAG NO.1

Tag no. 1

D02

TAG NO.2

Tag no. 2

D03

COMMENT1

Comment 1

D04

COMMENT2

Comment 2

D06

RESIST

Total resistance

D22

INPUT1 L_RNG

Input low range

D23

INPUT1 H_RNG

Input high range

D38

OUT1 DR

Direction of output-1 action

D39

OUT2 DR

Direction of output-1 action

D60

SELF CHK

Self-check result

E

SET(ALM)

Setting (alarm output)

*2

E03

SET POINT1

Alarm-1 setting

E04

SET POINT2

Alarm-2 setting

E05

ALM1 ACTION

Direction of alarm-1 action

E06

ALM2 ACTION

Direction of alarm-2 action

E09

HYSTERESIS1

Alarm-1 hysteresis

E10

HYSTERESIS2

Alarm-2 hysteresis

E11

ON DELAY1

Alarm-1 ON delay setting

E12

ON DELAY2

Alarm-2 ON delay setting

E13

OFF DELAY1

Alarm-1 OFF delay setting

E14

OFF DELAY2

Alarm-2 OFF delay setting

E15

RL1 ACTION

Direction of alarm-1 relay action

E16

RL2 ACTION

Direction of alarm-1 relay action

E60

SELF CHK

Self-check result

F

SET(COM)

Setting (communication)

*2

F01

PROTOCOL

Communication protocol

F02

ADDRESS

Address

F03

BAUD RATE

Baud rate

F04

PARITY

Parity

F05

DATA LEN

Data Length

F06

STOP BIT

Stop bit

F07

INPUT DEC PT

Decimal point position of input

F60

SELF CHK

Self-check result

P

ADJUST

Adjustment

P10

ZERO ADJ1

Zero adjustment of input

P11

SPAN ADJ1

Span adjustment of input

P12

OUT1 0%

0% adjustment of output-1

P13

OUT1 100%

100% adjustment of output-1

P14

OUT2 0%

0% adjustment of output-2

P15

OUT2 100%

100% adjustment of output-2

P60

SELF CHK

Self-check result

Q

TEST

Test

Q02

OUT1 TEST

Forced output-1

Q03

OUT2 TEST

Forced output-2

Q04

ALM1 TEST

Forced output (alarm)

Q05

ALM2 TEST

Forced output (alarm)

Q60

SELF CHK

Self-check result

*1

The Status is displayed for service personnel to see history

records.

*2

There are items not displayed depending on what output-2

is specified.