6. PARAMETER SETTING ORDER AND PRECAUTIONS

When setting a parameter, begin with Step 1 below and continue in sequence.

Range code No.

(IN)

You can begin with any of these parameters.

Alarm-1 action Alarm-2 action Alarm-3 action Alarm-4 action

(AL1)

(AL2)

(AL3)

(AL4)

After that, you
may proceed with
settings beginning
at any parameter.

Step 2

Step 1

NOTE

If the settings for the range code No. (IN) or alarm actions (AL1 to AL4) are changed, the
relevant parameter setpoints shown in the table below will be initialized.
To change a parameter setpoint, begin with Step 1 above and continue in sequence.

Parameters to be initialized if the range code No. (IN) is changed

Alarm setpoints (A1 to A4), hysteresis (HY1 to HY4), setpoint (SP)

Max. and min. monitor output values (RTH, RTL)

Input adjustment point LOW (BL) and HIGH (BH), input adjustment LOW (AL) and HIGH (AH),

wiring resistance correction (WIR)

High and low limits for PV display color change (PCH, PCL)

Parameters to be initialized if the type of alarm action (AL1 to AL4) is changed

The alarm setpoint (A1 to A4) corresponding to each alarm action (AL1 to AL4)

(Example: If AL1 is changed, A1 will be initialized.)

Parameters to be initialized if the type of PV display color mode (PCM) is changed

High and low limits for PV display color change (PCH, PCL)

7. SETTING INPUT-RELATED PARAMETERS

7.1

Setting Ranges and Factory-Set Values of Input-Related Parameters

Setup Parameter Screen 2

Parameter Name

Setting Range

Factory-Set

Value

Parameter

Symbol

61

or

the range

code No.

specified at

the time of

oreder

According to

the suffix

codes specified

at the time of

order

OFF

Range code No.
(IN)

Burnout action
(BSL)

Note:

When used with BARD-700, use the H range.

Ranges other than H range cannot be used for BARD-700.

Wiring resistance
correction
(WIR)

Instrument input range

Range code No.

Input type

H range

M

range

H

range

M

range

H

range

M

range

M

range

H

range

M

range

H

range

M

range

H

range

M

range

M

range

-199.9 to 660.0

°

C

-199.9 to 200.0

°

C

-199.9 to 660.0

°

C

-199.9 to 200.0

°

C

-199.9 to 510.0

°

C

-199.9 to 190.0

°

C

-199.9 to 649.0

°

C

80.0

to

930.0

K

80.0

to

470.0

K

80.0

to

930.0

K

80.0

to

470.0

K

80.0

to

780.0

K

80.0

to 460.0 K

80.0

to

920.0

K

Pt100

(ITS-90)

Pt100

(IPTS-68)

JPt100

(JIS’89)

Pt50(JIS’81)

Pt100

(ITS-90)

Pt100

(IPTS-68)

JPt100

(JIS’89)

Pt50(JIS’81)

OFF (0), UP (1), DOWN (2)

OFF (0), ON (1)

7.2

Setting Range Code No.

This section describes an example of setting the range code No. (IN) to “62” (instrument
input range: -199.9 to 200.0

°

C).

NOTE

Note that setting the range code No. (IN) to a value other than those specified in Section
7.1 is invalid.

Step 1

Press fore more than
3 sec.

Press

.

Press

.

When you press the SET/ENT key for more than 3 sec. with the
Operation Parameter Screen displayed, the Setup Parameter
Screen 1 appears.

When the power is turned on, the PV screen of the Operation
Parameter Screen appears.

Press the UP or DOWN key to display "62" on the DATA display.

Press the SET/ENT key to accept range code No. "62."
This completes the process for setting the range code No.

Press the SET/ENT key again for more than 3 sec.
This causes the Operation Parameter Screen to appear.

Press this key for
more than 3 sec.

This completes the process for
setting the range code No.

The decimal point blinks during
data change.

Press the SET/ENT key to display parameter "LOC."

Press the DOWN key to display "-1" on the DATA display.

Press the SET/ENT key to display parameter "IN" for setting the

range code No. in the Setup Parameter Screen 2.

Setup Parameter Screen 1

Setup Parameter Screen 2

Operation Parameter Screen

The decimal point blinks during
data change.

Press or

to display "62."

Press

to display "LOC."

Press to display "-1."

Power ON

To the Operation Parameter Screen

7.3

Setting Burnout Action

This section describes an example of setting the burnout action to “UP.”
The procedure below begins with the condition in which the Setup Parameter Screen 2 is
displayed.

Press

.

This completes the process for
setting the burnout action.

The decimal point blinks during
data change.

Press the SET/ENT key to display parameter "BSL."

Press the UP or DOWN key to display "UP" on the DATA display.

Press the SET/ENT key to accept burnout "UP."
This completes the process for setting the burnout action.

Setup Parameter Screen 2

Press or

to display "UP."

Press to display "BSL."

7.4

Correcting Wiring Resistance

This section describes how to correct wiring resistance when an error occurs due to the
influence of the input wiring resistance.
Correct wiring resistance after completing the wiring.

5

4

6

A

B

B

Short-circuit at the cable end.

MVRK

The procedure below begins with the condition in which the Setup Parameter Screen 2 is
displayed.

Press the SET/ENT key to display parameter "WIR."

Press the UP or DOWN key to display "ON" on the DATA display.

Press the SET/ENT key to correct the wiring resistance.

Press

.

This completes the process for
correcting the wiring resistance.

The decimal point blinks during
data change.

Press or

to display "ON."

Press to display "WIR."

Setup Parameter Screen 2

NOTE

If the burnout action setting is changed, the wiring resistance correction is automatically
set to OFF (0).
Correct the wiring resistance again after changing the burnout action setting.

3