Yokogawa JUXTA M Series Digital Limit Alarms MVRK User Manual

Page 8

Advertising
background image

IM 77J04R31-01E 1st Edition : 2006.08.31-00

8

14. MAIN SPECIFICATIONS

Model and Suffix Codes

- 0 0 - /

Digital Limit Alarm (RTD Input Type)
General use type
Always 0
24 V DC

±

10%

100-240 V AC/DC (Operating range: 85 to 264 V AC/DC)
RTD input
Custom order
Alarm output (transfer contact [1a1b] ), 2 points
Alarm output (NO contact), 4 points
1 to 5 V DC
4 to 20 mA DC
Communication function (RS-485)
No monitor output
UP
DOWN
OFF (No burnout)
Without socket

Model

MVRK

Suffix Codes

Type

Power Supply

Input Signal

Output Signal

Monitor Output

Burnout

Optional Specification

3
6

1
2

6

A
P
N

U
D
N

-U

-Z

0

/SN

-0

Description

Input and Display

Number of inputs: 1 point
Input signal: Set the measured input range within the instrument input range. (Refer to

Section 7.1.)

Input resistance: 1 M

(4 k

during power off)

Allowable leadwire resistance: [Input span (

°

C )

ϫ

0.4 (

)] or 10

per leadwire, equal or

less than whichever is smaller. (Make the resistance of each wire the same.)

However, when used with BARD-700, this value can be added to the BARD

internal resistance.
Detective current: Approx. 0.5 mA
Maximum allowable input:

±

4 V DC

PV (measured value) display: 4-digit, 7-segment, red/green LED, character height of

13.5 mm

Data display: 4-digit, 7-segment, green LED, character height of 9 mm
Alarm indicator lamp: 2 orange LEDs for 2 points of alarms or 4 orange LEDs for 4

points of alarms. Lights up if an alarm occurs.

Economical mode: Turns off the indicating LED if no keystroke is made within the set

time.

Setting range: 0 (does not go off) or 1 to 60 minutes

Active color PV display (PV display color changing function): This function changes the

PV display color from green to red or from red to green according to the set
PV display color mode shown below.

[PV display color mode to be set]

Link to alarm 1: Links to alarm 1.
Link to alarm 1 and alarm 2: Links to alarm 1 and alarm 2.
Link to alarm 1 to alarm 4 (only for 4 points of alarms): Links to alarm 1 to alarm 4.
SP deviation: Changes the PV display color according to whether measured value is

less than SP deviation high limit or SP deviation high limit or more; whether
measured value is more than SP deviation low limit or SP deviation low limit
or less.

PV limit: Changes the PV display color according to whether measured value is less

than measured range high limit or measured range high limit or more;
whether measured value is more than measured range low limit or measured
range low limit or less.

Fixed color: Fixes PV display color in green or red.

Output

Signal type: Relay contact
Number of outputs: 2 points of contact outputs (transfer contact [1a1b] ) or 4 points of

contact outputs (NO contact)

Contact rating: 120 V AC/1 A, 220 V AC/0.5 A (resistance load)

30 V DC/1 A, 120 V DC/0.1 A (resistance load)

Alarm action:

PV high-limit alarm

PV low-limit alarm

Deviation high-limit alarm

Deviation low-limit alarm

Deviation high and low-limit alarm

Deviation within high and low-limit alarm

Energized or de-energized under normal condition

Energized or de-energized under normal condition

Energized or de-energized under normal condition

Energized or de-energized under normal condition

De-energized under normal condition

De-energized under normal condition

Alarm action

Relay action

Alarm setting range: Within the input range

Setting resolution: 1 digit (0.1

°

C)

Setpoint setting: Virtual setpoint when the deviation alarm occurs

Setting range: Within the input range
Setting resolution: 1 digit (0.1

°

C)

Hysteresis setting range: The value resulting from adding a hysteresis value to an alarm

setpoint should be within the set input range.

Setting resolution: 1 digit (0.1

°

C)

Alarm ON delay setting: Condition monitoring time from the establishment of alarm

conditions to its output

Setting range: 0 to 999 seconds
Setting resolution: 1 second (However, about 0.2 second is to be added to the set time

to prevent wrong operation.)

Alarm OFF delay setting: Condition monitoring time from the establishment of return-to-

normal conditions to its output

Setting range: 0 to 999 seconds
Setting resolution: 1 second (However, about 0.2 second is to be added to the set time

to prevent wrong operation.)

Monitor Output

Analog Output

Output signal: 1 to 5 V DC or 4 to 20 mA DC
Allowable load resistance: 2 k

or more for 1 to 5 V DC

350

or less for 4 to 20 mA DC

Output variable range: -6 to +106%
Output scaling: Set any value within the measured input range. (Set the value so that

the input range corresponding to the output scaling is 10

°

C or more.)

Output accuracy:

±

0.1% of output span

However, the accuracy is limited in the following cases according to the output

scaling setting.

When the input range corresponding to the output scaling converted into resistance is

less than 130

in the instrument input range H:

Accuracy=

±

0.1 (%)

ϫ

130 (

)

Input range converted into resistance (

)

(%)

When the input range corresponding to the output scaling converted into resistance is

less than 38.6

in the instrument input range M :

Accuracy=

±

0.1 (%)

ϫ

38.6 (

)

Input range converted into resistance (

)

(%)

Communication Output (RS-485)

The MVRK can be connected to a personal computer, graphic panel, Yokogawa’s
programmable controller FA-M3 or programmable controllers of other manufacturers.

Standards: EIA RS-485
Maximum number of connectable units: 31 units
Maximum communication distance: 1200 m
Communication method: 2-wire half duplex, start-stop synchronization, non-procedural
Baud rate: 1200, 2400, 4800 or 9600 bps
Data length: 8 or 7 bits
Stop bit: 1 or 2 bits
Parity: Even, odd or none
Communication protocol: PC link, PC link with SUM, MODBUS ASCII, MODBUS RTU or

Ladder

PC link communication: Communication protocol with a personal computer, graphic

panel or UT link module of FA-M3

MODBUS communication: Communication protocol with a personal computer

(SCADA).

Ladder communication: Communication protocol with ladder communication module of

FA-M3 and programmable controller of other manufacturers.

Standard Performance

Input display accuracy:

±

0.1%

±

1 digit of instrument input range span

Alarm action point setting accuracy:

±

0.1%

±

1 digit of instrument input range span

Response speed: 500 ms (Time to alarm output when the input change is 10 to 90% and

alarm setpoint is 50%. When the alarm delay setting and hysteresis are
minimum.)

Burnout: UP, DOWN or OFF

Burnout time: 60 seconds or less
Action: High-limit alarm output for UP, Low-limit alarm output for DOWN

Insulation resistance: 100 M

/500 V DC between inputs, alarm outputs, power supply

and monitor output mutually.

Withstand voltage: 2000 V AC/minute between inputs, (alarm outputs 1, 2, 3 and 4),

monitor output and power supply mutually.
However, the following is excluded.

1000 V AC/minute between (alarm outputs 1 and 4) and (alarm outputs 2 and

3) and between inputs and monitor output.
(For 2 points of alarms, alarm outputs 3 and 4 are excluded.)

Power supply voltage: 24 V DC

±

10%, 100-240 V AC/DC (-15%, +10%) 50/60Hz

Power consumption: 24 V DC 2.7 W, 110 V DC 2.5 W, 100 V AC 4.2 VA,

200 V AC 5.4 VA

Effect of power supply fluctuation:

±

0.1% of span or less for the fluctuations within the

allowable range of each power supply specification

Effect of ambient temperature change:

±

0.2% of span or less for a temperature change

of 10

°

C

Effect of leadwire resistance change:

±

0.2

°

C or less for a change of 10

Ω/

leadwire

Mounting, Appearance and Environmental Conditions

Construction: Plug-in type
Material:

Casing; ABS resin (black), UL94 V-0
Socket; Modified polyphenylene oxide resin, including glass fiber (black),

UL94-V1

Mounting method: Wall or DIN rail mounting
Connection method: M3.5 screw terminal for input/output and power supply

3-pin 2-piece connector for monitor output

External dimensions: 51 (W)

ϫ

86.5 (H)

ϫ

133 (D) mm (including a socket)

Weight:

Main unit; approx. 270 g
Socket; approx. 80 g

Operating temperature range: 0 to 50

°

C

Operating humidity range: 5 to 90% RH (no condensation)
Operating conditions: Avoid installation in such environments as corrosive gas like

sulfide hydrogen, dust, sea breeze and direct sunlight.

External Dimensions

103

133

50

*1 To be added when the monitor output is specified.

Monitor output
terminal *1

10

30

3.3

7.8

2-Ø4.5

Mounting hole
(depth: 24.5)

DIN rail

40

35.4

81

80

86.5

85

Main unit

Socket

51 max.

11-M3.5

ϫ

7

screw

Unit: mm