Setting parameters – Yokogawa JUXTA FT5V Thermocouple Converter (Free Range Type) User Manual

Page 3

Advertising
background image

3

IM 77J08T05-01E 1st Edition

2007.01.15-00

M4 screw terminals are provided for the connection of external
signals. Attach a crimp-on lug to each wire for connection to the
terminals.
●Recommended cables: A nominal cross-sectional area of 0.5
mm

2

or thicker for signal cables, and that of 1.25 mm

2

or thicker

for power cables.

Wiring Diagram

1

2

4

5

6

7

3

6
7

4
5

RJC


Input(RJC)

Output

Power supply

2
3

DO NOT use the terminal

NOTE

●The power line and input/output signal lines should
be installed away from noise-generating sources.
Otherwise accuracy cannot be guaranteed.
●Adhere strictly to the specifications to avoid

overheating or damage. Before turning on the power,
ensure the following:
(a) Power supply voltage and input signal value

applied to the product should meet the required
specifications.

(b) The external wiring to the terminals and wiring to

ground are as specifications.

●Do not operate the product in the presence of

flammable or explosive gases or vapors.

●The product is sensitive to static electricity; exercise

care when in operation. Before you operate the
product, touch a nearby metal part to discharge
static electricity.

●Connect the RJC sensor to the terminal of the

converter together with the input signal line so that
the crimp-on lug of the input signal line overlaps the
RJC sensor.

●Handle the RJC sensor lead wire with care to prevent

disconnection.

Power Supply and Isolation

Power supply voltage: 24V DC ±10% (ripple: less than 5% p-p)
Current consumption: FT5A 65mA, FT5V 50mA
Insulation resistance: 100MΩ at 500V DC between input, output

and power supply mutually

Withstand voltage: 1500V AC/minute between input-output,

input-power supply

500V AC/minute between output-power supply

4. SETTING PARAMETERS

The parameters are set as you specified in your order. Refer
to the following to change the default settings.
Set the parameters using a PC (VJ77 Parameter Setting Tool)
or the Handy Terminal. Refer to "5. List of Parameters" in this
manual and the User’s Manual for VJ77 PC-based Parameters
Setting Tool (IM 77J01J77-01E) or the User’s Manual for JHT200
Handy Terminal (IM JF81-02E). Parameters are shown in
brackets "[ ]".

Connection of Setting Tools

VJ77 Dedicated adapter (E9789HA)

[Provided with VJ77]

PC with VJ77 installed

Dedicated cable (E9786WK)

[Provided with VJ77]

*Be sure to use the VJ77 of version R1.05 or later.

JHT200

Handy Terminal

JUXTA communication cable

3 pin connector (F9182ED)

[Provided with VJ77 and JHT200]

Setting Thermocouple Type

Set the thermocouple type to be connected to the input in

[B06: TYPE].

Display

Measuring range

Measuring span

K TYPE

-270 to 1372°C

3mV or more

E TYPE

-270 to 1000°C

J TYPE

-210 to 1200°C

T TYPE

-270 to 400°C

R TYPE

-50 to 1768°C

S TYPE

-50 to 1768°C

B TYPE

0 to 1820°C

N TYPE

-270 to 1300°C

Setting Temperature Unit

Set the temperature unit of the input range in

[B09: UNIT].

NOTE

Do not set the "-----" as the temperature unit, even if it
is displayed during the setting.
Otherwise it may cause the malfunction or damage.

Setting Input Range

Set the zero percent value of input range in

[B0: ZERO], and

the span of input range in

[B: SPAN].

Setting Burnout Action

Set the burnout action in

[B2: BURN OUT].

Set "OFF", "UP", or "DOWN."

NOTE

The wire resistance compensation should be applied
when the setting of input range, burnout action
direction or input wiring has been changed.

Advertising
This manual is related to the following products: