List of parameters, Maintenance,  calibration apparatus – Yokogawa JUXTA FT5V Thermocouple Converter (Free Range Type) User Manual

Page 4: 2 calibration procedure

Advertising
background image

4

IM 77J08T05-01E 1st Edition

2007.01.15-00

5. LIST OF PARAMETERS

Parameter Display

Items

A

DISPLAY

Display

A01

INPUT

Input value

A02

OUTPUT

Output value

A03

STATUS

Status (*1)

A04

REV NO

Revision number.

B

SET

Setting

B01

TAG NO.1

Tag number 1

B02

TAG NO.2

Tag number 2

B03

COMMENT1

Comment 1

B04

COMMENT2

Comment 2

B06

TYPE

Input type

B09

UNIT

Unit

B10

ZERO

Zero (0% of input range)

B11

SPAN

Span (Input span)

B12

BURN OUT

Burnout

C

ADJUST

Adjustment

C01 OUT 0%

Output 0% adjustment

C02 OUT 100%

Output 100% adjustment

C03 WIRING R

Wire resistance compensation

C04 ZERO ADJ

Input zero adjustment

C05 SPAN ADJ

Input span adjustment

C08 RJC

RJC on/off (*2)

*1:

This “STATUS” is for the customer’s engineer to check the history.

*2:

The RJC returns to ON after the power is turned off and then on again.

6. MAINTENANCE

The product starts running immediately when the power is turned
on; however, it needs 10 to 15 minutes of warm-up before it
meets the specified performance.

6. Calibration Apparatus

A voltage current source (Yokogawa 7651 or equivalent)
A digital multimeter (Yokogawa 7561 or equivalent)
A precision resistor of 250 Ω ±0.01%, 1W
A setting tool for adjustment (Refer to "4. Setting Parameters"
in this manual.

6.2 Calibration Procedure

1. Connect the instruments as shown below.

1

2

3

4

5

6

7

3

2
3

6
7

4
5

24V DC

Ro

DMM

Voltage

current

source

Input

Output

Ro: 250Ω precision resistor for

current output

Setting tool

Power supply

2. Turn off the RJC using the setting tool.
3. Use the voltage current source and apply the electromotive

force equivalent to 0, 25, 50, 75, and 100% of the measuring
range to the converter.

4. Verify that the corresponding output voltages are 0, 25, 50, 75,

and 100% respectively and within the specified accuracy rating.
(R

o

is used for current output.)

Use the setting tool (VJ77 Parameter Setting Tool or JHT200
Handy Terminal) to adjust the input/output signals.




Turning the RJC on/off

(1)

Read the parameter

[C08: RJC].

(2)

Select "ON" or "OFF" in the parameter

[C08: RJC].

NOTE

The RJC returns to "ON" after the power is turned off
and then on again.

Input Adjustment Procedure

(1)

Input the value equivalent to 0% value of the input range
to the converter.

(2)

Read the parameter

[C04: ZERO ADJ] and check the

input value.

(3)

Select “INC” or “DEC” in the parameter

[C04: ZERO

ADJ] to adjust.

INC: Increase (Adjusts the increased value of the input
[voltage] value)

DEC: Decrease (Adjusts the decreased value of the
input [voltage] value)

RST: Reset of the adjustment value

(4)

Input the value equivalent to 100% value of the input
range to the converter.

(5)

Read the parameter

[C05: SPAN ADJ] and check the

input value.

(6)

Adjust the span in the same way as (3).

Output Adjustment Procedure

When adjusting 0% value of output:
(1) Set the adjustment value 0% in the parameter

[C0:

OUT 0%].

•The value equivalent to 0% of the output range will be
output, irrespective of the input.

(2) Check the output value via digital multimeter, and adjust

it in the parameter

[C0: OUT 0%].

•If it slips out to the (+) side, set (−) value equivalent
to slipout; if it slips out to the (−) side, set (+) value
equivalent to slipout for adjusting the output value to
0%.

*: The 100% value of output can be adjusted by the same

operation as the above in

[C02: OUT 00%].

Wire Resistance Compensation

(1)

Short-circuit at the sensing end of the field side.

FT5A

FT5V

Short-circuit at the cable end

(2)

Read the parameter

[C04: ZERO ADJ] and make sure

the setting is "RESET".

(If the setting is "EXECUTE, select "RESET". The
compensation value will be reset.)

(3)

If "EXECUTE" is selected in the parameter

[C03:

WIRING R], the wire resistance compensation will be
done automatically.

For adjustment using a setting tool, refer to the User’s Manual for
each setting tool and “5. List of Parameters” in this manual.
User’s Manual for VJ77 [Document No.: IM 77J01J77-01E];

however, use the VJ77 of version R1.05 or later.

User’s Manual for JHT200 [Document No.: IM JF81-02E]

Advertising