CONTRACT

OR

16.2

Take the 5/16 dia. plastic tube and push one end on the connector located at the bottom of the overfl ow

pan. Please see Fig. 16b and Fig. 16c.

16.3

Install the overfl ow pan under the tank by sliding the slot on the back screw and hooking the key hole

on the front screw. Please don’t tighten the screws.

16.4

Reconnect the white wire for the overfl ow sensor on the overlow pan.

16.5

Cut the two drain tubes and insert them in the rigid pipe. Note that the main silicon drain tube must

have a minimum length of 18” to allow the siphon to work properly. It is important to leave an air gap
between the soft tubes and the rigid pipe.

16.6

Open the water supply valve (fully counter-clockwise) to bring water to the humidifi er and let the water

pressure enter the system.

16.7

Follow the water supply path completely and carefully check for leaks at the fi ttings.

Fig. 16c

Fig. 16d