Contract or, Countinuous on – Thermolec AcuSteam User Manual

Page 33

Advertising
background image

Page 31

CONTRACT

OR

Number of

fl ashes

of the red light

Error Description

Humidi

fi er

Status

Actions

to

be

T

aken

by the T

echnician

Reset

OFF

No error

The humidi

fi er is working

fi ne

None

Countinuous

ON

The

fl ood sensor under the tank

senses water in the pan.

Humidi

fi er immediately suspends the

ongoing operation. Heating elements and

supply valve are switched of

f.

The power

green light is blinking.

Turn power of

f. Check for leaks around the

tank clamp, SW valve and drain tube. Make

sure tank arrows align and gasket is sealing

properly

.

Automatic Reset when

Over

fl ow pan dries up.

1

The two water level sensors are

miswired or do not read the water

level properly

.

Humidi

fi er attempts to operate, then stops

because of wrong information from water

level sensors.

The power green light is

blinking.

Turn power of

f. Clean or replace HLS or LLS

water sensors. Check for proper wiring of

HLS and LLS sensors.

Automatic Reset when

switching main power ON

3

Inadequate water supply

. The

supply valve was open for more

than 6 minutes.

Humidi

fi er immediately suspends the ongo-

ing operation. Heating elements and supply

valve are switched of

f.

The power green

light is blinking.

Turn power of

f. Check SW valve circuit for

24V DC at the valve. Refer to manual (p. 20)

and check for proper drain installation. Make

sure SW shut-of

f valve is open, SW valve is

responding and SW tube is clear of debris.

Automatic Reset after

5 min or when switching

main power of

f and on

4

Inadequate drainage.

The tank

did not drain or the draining cycle

is too long.

Humidi

fi er immediately suspends the

ongoing operation. Heating elements and

supply valve are switched of

f.

The power

green light is blinking.

Turn power of

f. Check for proper drain setup

by referring to manual (p. 20). Check and

clean tank, SS siphon tube and silicon drain

tube if necessary

.

Automatic Reset when

switching main power ON

5

The air pressure switch does not

detect enough air pressure OR

the high limit HST

AT

(optional)

senses extremely high humidity

in the duct.

Humidi

fi er immediately suspends the

ongoing operation.

The unit goes back

to normal operation as soon as the error

condition disappears.

The power green light

is blinking.

Check if the FF motor is running. If not, turn

FF to continuous operation. Check

fl ow

sensor

(pitot tube) in duct for blockage, then make

sure plastic tube is connected properly from

fl ow sensor to PD switch under PC board in

unit (see manual). Change furnace

fi lter

if

needed.

Automatic Reset

when error conditions

disappear

6

Temperature inside the tank

exceeded the high temperature

cut-out setting.

The high temperature cut-out has tripped.

The humidi

fi er immediately suspends the

ongoing operation. Heating elements and

supply valve are switched of

f.

The power

green light is blinking.

Turn power of

f.

This is a serious condition and

will likely require assistance from a service

technician. Call 1-800-336-9130.

After pushing on the

thermal cut-out button,

automatic reset when

switching main power ON

22.

Detailed Error Codes

Legend: SS = stainless steel, FF = furnace fan, SW = supply water

, HLS = high level sensor

, LLS = low level sensor