Purge

1. Slowly turn the Control Valve and

stop half way and hold for 3 minutes
as indicated to purge flushing solvent
from component and lines. Proceed
to the next step after 3 minutes.

2. Continue slowly turning the Control

Valve towards PURGE. Wait one
minute before proceeding with the
next step.

3. Turn the Selector Valve to PURGE.

4. Purge the component for a minimum of 30 minutes to ensure that it is completely

dry.

5. Turn the Control Valve to OFF.

6. Disconnect the “IN” and “OUT” hoses from the adapter fittings.

7. Disconnect the adapter fittings from the component.

8. The Coalescing Filter will need to be drained periodically. Turn the drain valve at the

bottom of the filter counter clockwise. A small amount of water may drain. Some
shops may have a coalescing filter already inline. In this case very little moisture
may be present.

Repeat the flush procedure on the next component until all
components have been flushed.